hi frienda We have 250kva cater pillet dg set we are fasing
one diffrent proublam in dg we are start dg set after one
mint applying load around 450a load but dg was run 3 Or 4
mints after 3 mints dg was shuding down automatic how to
face this proublam pls tel any budy
Answer Posted / abdulgafar
A full load current of 250KVA DG Set is approximatly 350A.
Most of the DG Sets are designed to catter approximatly 10%
over load For a period of one hour hence a 250KVA dg set
can catter 385A For a period of one hour. you have applied
more load then the DG Set can catter/ deliver hence your DG
Set is triping automatically after about 3 min. hope i have
answered your question.
AGM
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
We have 110Vac ,10A ac supply which is converted into 110VDC & How much DC current? which factor is reqired for dc current calulation?
i want to put single phase load on scott connected transformer,eventhough how to balance the transformer.
HOW TO REDUCE POWER PLANT AUXILIARY POWER CONSUMPTION?
ASTM D 3455 - Standard Test Methods for Compatibility of Construction Material with Electrical Insulating Oil of Petroleum Origin has been used for Testing Transformer Oils with a product placed in it. Aged Control Oil has a Power Factor of 0.032% at 100°C. Aged Oil with a Test component has a Power Factor of 0.093% at 100°. Is this increase acceptable? If not why? How much increase is acceptable?
Classify driling machines.
In general bus riser follows the bus section in SWGR. What are impacts if bus section follows bus riser?
mccb service sittings be done?
in ACB breaker requireding 3200Amps. buscoupler getting OFF mode and again it reset and getting normal position give me a required answer?
different aspects of voltage stability
use of choke in APFC panels
what are the available sizes of pin type terminal lugs in the market today?
Is MEN and RCD related to each other ?? IF yes then how??
tan delta equation test on alternators
why the carbon brushes are broken in srim while the motor runningtime
what happen if the load connected to the induction motor is taken away? the same question for synchoronous generator in synch i think that the the exitation voltage will appear on the terminal only if so plz answer me