If Two Generators are working parellel in a network and
suddenly the field of one Generator get weakened What will
happened if there is no reverse power relay fixed in that
Generator panel????
Answer Posted / k.prakashchandra
Less excitation?. Then the generator will continue share the
load at leading power factor resulting in higher armature
current as the prime mover is still running and the terminal
voltage of the Gen is reduced.If this current exceeds the
set value ,Gen will trip on OCR which does not allow for
very low pf.
Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
Can I use distributon class/transmission class Lightning arresots for protecting the building? If not why please explain?
Why 9KV surge arrester having 7.65KV of MCOV?
what is difference between elr and R eartl realy.
How to detect voltage vector shifting in interconnection protection.
DEAR SIR/MADAM,CLEARLY EXPLAIN ABOUT CRAWLING AND COGGING EFFECTS IN INDUCTION MOTOR.
Brief me about maintenance planning & sheduling of machine tool.
percetans
how to select the double earth conductor if 21A full load?
How to run a three phase motor into single phase........
can any one tell me about the Extra low voltage systems?From where we give supply to these type of systems??
why power not passes in plastic and rubber material
IN MY SYSTEM THERE IS ONLY OVER CURRENT EARTH FAULT RELAY IS AVAILABLE. FOR THE UNBALANCE SENSING IS THERE ANY RELAY IS AVAILABLE? THE SAME CTs WHICH ARE USED FOR THE OVER CURRENT EARTH FAULT RELAY CAN USE FOR UNBALANCE ALSO?
What is MSL designation of a motor and same may be provided in details.
How to decide and select the different earthing wire size for the different types of earthing
Why saturation region slowly shifted in the left side?