when running 2 nos 450kva dg sets in parallel operation ,in
one Dg set power factor and Kvar going to lagging and ampere
suddenly going high,please give me suggestion to correct the
same.
Answer Posted / nithi
mr.prakash answer is correct........over excitation of one
DG set & under excitation of another Dg set will lead to
this type of problem.so, check both DG set AVR circuitary
(voltage set value).
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
how does it help for selection of a transformer.
Pl. give me checklist for installation & commissioning of machine tool.
what is the advantages og idmt relay over magnetic relay??
What is EHT tariff or Power factor Tariff ????
please give some hindalco placement papers for written exam
what are the interview question asked in wind mill about electrical
how many safety really of DG sets.
A powerplant has 8 gensets operating in grid parallel mode. In one genset sometimes there is pf variation and kvar variation. The plant operates in pf mode. When this variation is observed the load is stable, voltage is also stable, freq and genset speed is also stable. How will you check the functioning of pf card. What shall be the ideal output vdc of the pfc, from there it is input to AVR?
Why IR value of the (HT cable Plus synchronous motor) is less while individually having IR values in GΩ?
what is the difference between transformer,converter and transducer
10 tube light connect in mcb breaker.one tube light is fault.so breaker is tribe.how fault is rectified.(using 3wire phase,earth,neutral)
How can get elongation of 2 k.G aluminium, if elongated aluminium dia is 2.5 mm?
i need to now what will be the cable size to the following load, transformer to distribution panel distance 110m, load 1000kw, voltage 400v, pf 0.85, permissible voltage drop 2.0%, overhead line, atmospheric temperature 35 degree c.
Circuit diagram of tube light without starter using electrical choke
Please clarify 1. Icw: rated short circuit working withstand capacity 2. Icu: Rated ultimate breaking capacity 3. Ics: Rated service short circut withstand capacity 4. other specification of ACB