when running 2 nos 450kva dg sets in parallel operation ,in
one Dg set power factor and Kvar going to lagging and ampere
suddenly going high,please give me suggestion to correct the
same.
Answer Posted / nithi
mr.prakash answer is correct........over excitation of one
DG set & under excitation of another Dg set will lead to
this type of problem.so, check both DG set AVR circuitary
(voltage set value).
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
IN electrical field, WHAT ALL THINGS THE CUSTOMER WILL ASK WHILE ORDERING FOR LT PANEL (ALL TYPES OF LOW TENSION PANEL)
How much inductance or resistance require as a starter in series with induction motor of specific capacity(e.g. 5 hp) ? What is formula for it ?
is that a problem if i connect a single phase load to a secondry delta connected transformer but i get a neutral from other transformer i the system?
please send me previous year questions of jspl through which i could prepare myself for the test.
For the requirement of a furnace of temperature range up to 1200 oC using silicon carbide rods, What is the required rate of transformer needed (please do it with all details)?
in an electronic tri vector meter when the current and voltage sequence changes ? what is the effect of phase sequence on recording of meter
How do you compute voltage drop and cable size over distance?
write encoder 17 pins details? pin a;b+, pin b;w+,..pin s & t. what is the meaning of b+, w+? explain;
Why we find the sensitivity for the CT's to check?
Dyn1 transformer vector group testing how to do
how the synchronizing is obtained at bus couplers in grid substation? (because there we cannot change the frequency in one of transmission lines like in generator synchronization)
Why in power plant projects we see DOL starting method used for motors upto 160 kW instead of star delta method
how to select the mpcbs and contactor for 3 phase 30 hp star delta motors.for plc control.and tell me the calaculation for future use.
what is the minimum voltage require to injure our body?
What are the causes of unbalanced current on 34.5kv feeder Ia=0.05,Ib= 0.25, Ic=0.15 and In=0.27 prior to tripping current are balance?