Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

What happen if 1200KW/1500KVA alternator runs at no load
and high R.P.M.for one minute?

Answer Posted / k.prakashchandra

There are over speed and over voltage relays to
protect.Governor becomes helpless if there is sudden throw
off of load,then over speed relay of the governor shuts down
the prime mover.With AVR, voltage does not increase.However
generators are designed to withstand runaway speeds for
short periods. Bearings are first to get damaged under
prolonged high speeds.Governors can also be made not to
allow for undesired high speeds with the help of braking
systems, if they are employed.

Is This Answer Correct ?    1 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

determine two methods to find loose connection in operational electrical system?

1628


I have done my m.tech in electrical engg discipline. Can any one please suggest me how should I prepare for getting into phd in iit or nit.How should I prepare for getting into lecturership

1640


What is the formula for calculating no-load current?

1049


1. If 8.35%Z means the percentage impedance of 132kV-line from power company, we will like to reconfirm its base capacity.

1938


please explain how to do 'pole drop test' on generator?

2853


What is difference between safe PLC and normal PLC

1534


In layman terms, what is the difference of Dielectric strength and dielectric constant when speaking of an insulating oil

2622


Either the Armoured Earthing strip of HT 3 core cable have to pass through CB CT or not , why ???

2021


What is frantic effect?

1202


how to select proper cable for ct wiring so that drop within the limit.

1928


3 shows a 415 V, 3-phase generator supplying a 3-phase 415/110 V transformer. Draw the individual and combined impedance diagrams to a base of 10 kVA. Determine the system fault kVA and the fault currents at the 415 V and 110 V busbars for short circuit faults on the transformer input or output terminals. Work in p.u. values of impedances.

2614


can u tell me the promotion from oiller to enginer

1880


what are the dimensions for 200 kva transformer plinth (plateform),in which pcc m20 is used..

11595


how to find the voltage's of a transmission line plzz help with pictures i am not able to understand

1298


Explain Even and Odd signals?

1843