Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

i have one transformer 1000kva, 11/.433kv. we are using
200/5 amp. ct unit for measuring purpose, & one 800 amp.
V.C.B Unit for the same t/f operate, i wants to known the primary
current of T/F is only 53 amp. why we used 800 amp.
V.C.B ? & 200/5 amp. CT Unit.

Answer Posted / a k kataria

Well given the rating of transformer as 1000 kva, CT ratio
should have been 100/5. As far as VCB current rating is
concernd,these are generally made for universal
applications and are generally 630 Amps onwards 'cause in
the eventuility of fault ,heavy currents are to be taken
care of.More over increase in the rated current capacity of
breaker adds little to the cost compared to other
components of the breaker.There fore capacity of VCB is OK.

Is This Answer Correct ?    2 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What are factors to be considered while we selecting the Core Balance Current Transformer for Earth fault protection

1867


what r PID controllers?why they r used?what is there purpose?plz Explain in detail

2068


Usually in the L & T make MCC feeders' power circuit,we have BMR after the MAIN CONTACTOR.,can we interchange their position, keeping the control logic same???

2093


What is Diff btw Fire Alarm & VESDA System???

2390


Is it possible to implement Restricted Earth Fault protection for a transformer without neutral CT?

4375


How to calculate approximate load loss of a distribution transformer by knowing %ge imp of transformer?

2209


what are the advantage and dis-advantage of 3 phase 4 wire energy meter?

2188


If we want to change a contactor of faulty one what are the conditions want to fullfil

1979


What is the use of oil in transformers?

1096


HOW TO WORK A VFD?SAY SIMPLE METHOD

4413


Dry type transformers

1869


Why two phase welding machine is used instead of three phase welding machine.

1918


What is the method of estamating of cable, CB,MCB ?

2167


what is the differencce inn series and cascade connection??

4719


How will you define capacitance?

1151