Why no-load primary current is very small
as compared to full load current in transformer (as 1% of
full load current?
Answer Posted / masoom raza
when secondary is open circuit the current in primary
is low i.e only magnetizing is present to create flux
in core.but when load is connected in secondary side it
produces its own ampere turn N2I2 which reduces the flux
in core . in order to maintain the flux constant, primary current increases to balance N2I2 i.e
N1I1=N2I2(neglecting magnetizing current)
therefore primary current increases when load
is connected.
| Is This Answer Correct ? | 3 Yes | 3 No |
Post New Answer View All Answers
How to calculate the time setting for star connection in star delta starter? For example 10KW 3PH Induction motor.
Is a contactor (or master relay) required between incoming lines and a VFD? The question goes to safety. If a contactor were used before the VFD and an e-stop engaged then the motor will coast to a stop (i.e. VFD loses power) instead of stopping much faster if the VFD braking fucntion were used. It would make more sense to keep power on the VFD.
What are the specifications for conducting earth leakage test as per IEC standard?
how much flux density of CRNO core
what is difference between earthingpits,earthing grid & earthing mess?
what is inter connected dc generator?
sir i have cleared the apti test of EIL held on 15th march and my interview will be in new delhi on 2nd june.i will be very much helpful if u help me regarding the type of interview questions comes at EIL.(URGENT.........PLZZZZZZZZZZ...............)
description about dry type transformers
What is the use of bundle conductors?
Dear all, I just want to ask an expert on this forum for some insights. For the magnetic balance test, when applied voltage on a Delta-Star transformer e.g. Dyn11, the following relationships apply for HV side: 1. H1-H2 = H2-H3 H3-H1 2. H2-H3 = H3-H1 H1-H2 3. H3-H1 = H1-H2 H2-H3 For the LV side also: 4. X1-X0 = X2-X0 X3-X0 5. X2-X0 = X3-X0 X1-X0 6. X3-X0 = X1-X0 X2-X0 Is there a similar pattern for Y-d, Y-Y, D-d? And how about Y-z, D-z, Z-y transformers? I've tested a YNzn5 transformer and for LV side I don't see the pattern. In this particular case I got for LV side the following (see values below): H1-H0 H2-H0 H3-H0 X0-X1 X0-X2 X0-X3 128.0 119.9 7.2 29.2 13.3 15.8 70.7 128.4 59.2 23.4 22.0 3.6 7.2 120.1 128.1 13.4 29.3 15.8 What is the relationship here for LV? For row 1 I see the relationship, for row 3 I also see but it's shifted, but for row 2 I don't see such relationship. Any suggestions, answers, someone?
bus bar design conditions and sizing pls tell me quickly
what is rating boiler
sugest any typical project ?
WHAT IS THE TOTAL POWER GENERATION IN CHHATTISGARH?
Why does the adjacent zone of protection overlap?