we want install 11KV generator to supply power 12km far
from the power house.Load to be fed is 1MW.which conductor
should we use and wat will be transmission line losses?
Answer Posted / k.prakashchandra
The current is 52.5 A at unity pf, add 20 % .It is about 60
A. You can use Rabbit conductor