i am working in thermal power plant .
if temperature transmitter is not showing reading in dcs
then how can we rectify the problem?
Answer Posted / g kiran kumar
1. Check the wiring at all terminal blocks at field, at
control panel and at PLC for any loose connection.
2. Check the Transmitter supply.
3. Measure the output from Transmitter.
4. Check cable continuity.
5. Finally check the configuration of TAG in the DCS (may
be someone deleated accidently).
Is This Answer Correct ? | 6 Yes | 0 No |
Post New Answer View All Answers
How is automatic reference junction compensation carried out in temperature recorders?
What are primary elements of measuring pressure?
what is the calibration procedure for transweigh make weigh feeder?
In control valve proximity inductive sensor is taken as digital feedback for full open and full close.Normally its volts 24v when the sensor acts the feed back voltage 14v so that our relay not indicating in plc panel . kindly give the solution.
Explain pH, Conductivity.
Why humidity limit is 30 to 55 % for raw material storage?
what is performance test.need defination
Describe the functions of the Operator Interface including the considerations related to alarming and display layout/configuration/layers.
What is the working principle of the magnetic meter?
what is function of SCADA , and how is it work, explain with difination
what is stroke check for field instument transmetter's & AOV's
dear sir we have insatlled positioner model no.sipart PS2 make Siemens at our control valves . now problem is if we want to increase the response of valve opening speedy /fast. what parameters do we change for positioner ? any idea. please guide us.
in natural gas indirect water bath heater,how to prevent the problem of backfire from firetube during ignition...becoz of this backfire performance of wbh is going low.
what are the use of belew gear in general ??
Calibration of controller (pneumatic)