What is difference between Dy11 & Dyn11 vector group
transformer. Can both these transformers operate in
parrallel.
Answer Posted / ravi
Winding connection designations
High Voltage Always capital letters
Delta - D
Star - S
Interconnected star - Z
Neutral brought out - N
Low voltage Always small letters
Delta - d
Star - s
Interconnected star - z
Neutral brought out - n
Phase displacement
Phase rotation is always anti-clockwise. (international
adopted convention)
Use the hour indicator as the indicating phase displacement
angle. Because there are 12 hours on a clock, and a circle
consists out of 360°, each hour represents 30°.
Thus 1 = 30°, 2 = 60°, 3 = 90°, 6 = 180° and 12 = 0° or
360°.
The minute hand is set on 12 o'clock and replaces the line
to neutral voltage (sometimes imaginary) of the HV winding.
This position is always the reference point.
Because rotation is anti-clockwise, 1 = 30° lagging (LV
lags HV with 30°)and 11 = 330° lagging or 30° leading (LV
leads HV with 30°)
To summarise:
Dd0
Delta connected HV winding, delta connected LV winding, no
phase shift between HV and LV.
Dyn11
Delta connected HV winding, star connected LV winding with
neutral brought out, LV is leading HV with 30°
YNd5
Star connected HV winding with neutral brought out, delta
connected LV winding, LV lags HV with 150°
" So there is no specification of Dy11.. it will be Dyn11 "
| Is This Answer Correct ? | 63 Yes | 18 No |
Post New Answer View All Answers
plz send me HPCL apptitude paper.. maulik_elect@yahoo.co.in
Differentiate between magnetic field and magnetic flux?
how to find the capacitance value of the motor while running??
WHAT ARE THE EFFECTS OF SERIES RESONANCE AND PARALLEL RESONANCE ON THE CIRCUITS PARAMETERS?
What is the meaning of loop in transformer
what is the criteria for selection of conductor used for ehv ac electrical dischrge
I need the list of Universities who have summer intake for BS degree in Electrical Engineering.?
How do I calculate a WTI CT ofa 1250kVA 6600/400V transformer
What is the difference between line drop and percentage line drop?
why do we not use equivalent voltage source in negative sequence equivalent ckt.
Draw the line diagram of diffretial relay connected to transformer?
prove that power consumed in 3 phase delta system is 3 times as compared to 3 phase star system
I am shobana from Chennai. I am having my personal interview on 19th Dec at Chennai.kindly mail me the questions to mail id shobana.shanthi@gmail.com
What was your role in the silicon evaluation/product ramp? What tools did you use?
I Want randstand placement papers