what is reset windup in integral control?
Answer Posted / www.islamqa.com
"Reset windup" is a controller problem that occure when
there's an upnormal load disturbance, which make Pv away
from Sp although the controller is 100% o/p!!
in this case the controller will continue to integrate the
error signal upward, so we can say we have "reset wind
up ", and the valve (or final control element) is taking
its extreme position - up to this we have no problem.
# The problem starts when the unusual disturbance is away
and the controller extreme o/p will have an effect on the
Pv which now on it's way to equal Sp.
The problem now is that the controller seems like to
saturate at 100% due to time spent "winding up", Now we may
have Pv=Sp and the controller remain saturated at 100% o/p,
it will take a long time before the controller start to
downward its o/p value.
# Modern PID has "anti reset wind up" feature, which may
contain an algorithm to turn off the integral term in case
of error is exceed a specific value, or any other algorithm
to stop integral accumulation in case of winding up.
Regards,
Ahmed Sabry
Control and Instrumentation Engineer
GPC - General Petroleum Company
ahmedsabry.online@gmail.com
CELL.: 00 2 0121367310
| Is This Answer Correct ? | 13 Yes | 1 No |
Post New Answer View All Answers
How to convert mmWc(mili meter water colam) to tph(ton per hour)?
how many types of spped sensors n vibration sensors?their basic principle n connection?
hi,i am doing 3 year in electronic and instrumentation engineering. what type of aptitude questions will be asked in a core industries and how can i improve my skills in instrumentation?
how do calibrate the valves.. with clear manual
Differentiate between ultrasonic flowmeter and radar type flow meter
What is megering????
Calculate the maximum pressure drop that can be allowed to occur across a control valve, so that we can prevent cavitation / flashing from occurring. Use the following formula: Δ P allow = Km (P1 – PvapourA) where, Δ P allow - the maximum allowable differential pressure for sizing purposes, or terminal pressure drop; Km- the valve recovery coefficient from the manufacturer’s catalogue; P1 - absolute inlet fluid pressure; PvapourA - absolute fluid vapour pressure at the inlet temperature; Use Atmospheric pressure = 101.3 kPa, P1 = 1200 kPa(g), PvapourA = 4 kPa, KM = 0.72
what is the procedure of belt scale calibration?
HOW TO CHOOSE FREAQUENCY IN FMCW TYPE RADAR INSTRUMENTS. DESIGN BASIS OR DESIGN CALCULATONS ?
how do u calibrate the vacuum transmitter if it shows more reading
Why upper weighing limit of electronics balance is 90% of the total weighing capacity?
please any body have most important data for study for saudi aramco test of instrument QC thanks email shahnaveedullah@gmail.com
Calibration of controller (pneumatic)
I have completed B.E. Instrumentation & control in 2009. i have 3 year industrial job experience in chemical plant.now, I want to join M.E. in external. so, Plese say easiet way and good institute name.
which type of signal used in instrument?