how to install Differential pressure transmitter in gas
line.i need transmitter down side.
Answer Posted / www.islamqa.com
Bharathi is right, we have to use "condensation pot"
# Actually the gas is "self venting" and the instrument
mounting should be above the pipeline in order to avoid
vapor condensation which cuase fault reading.
# For liquid service the instrument mounting should be
below the pipeline as the liquid is "self draining".
# If we want to mount the instrument below the pipeline in
gas service we should use "condensation pot" and the
operator should drain it regularly to avoid fault reading.
# In steam service we use the condensation pot also and it
should be fully filled with water and its mounting should
be in the same pipeline level and the instrument itself
will be below the pipeline, this link indicte the situation:
http://www.eng-tips.com/viewthread.cfm?qid=166893&page=97
the aim of water filling is to provide a solid motion
transfer in order to have a good accuracy.
Regards,
Ahmed Sabry
Control and Instrumentation Engineer
GPC - General Petroleum Company
CELL.: 00 2 0121367310
| Is This Answer Correct ? | 14 Yes | 1 No |
Post New Answer View All Answers
I want to buy a seal kit of a pneumatic power cylinder.But I don't know it's specification.So please help me to know its specification.
What is PDS and PDMS ?
what is your eligibility criteria for freashers?
what is the calibration procedure for magnetic flow meter @ onsite
What denotes the 5/8mm in the 3300XL 5/8mm proximitor probe?
What are primary elements of measuring pressure?
Hello to all....I am an Instrumentation Graduate and i am passed out in this year only.. I am unable to find the job in my core instrumentation.. so any boby tell me how to and where to search the job....please...and also tell me i there are any courses offered in the instrumentation stream so i can do it... you can send your suggestions to my mail-id i.e Ganesh20084u@gmail.com ... please..
State some of balance principle’ advantages?
I faced several time siemens ps2 positioner automatically getting Chang in it's set point direction after auto calibration So is there any causes biside this or any permissives ?
What is zero elevation and zero suppression?
What is profibus?
A DP transmitter is used to measure the level of an open tank. The drain line of the tank is connected to a control valve, and is configured as, if the level of the tank is 90% the valve should get open 10%. And if the tank level is 10%, the valve should get open 90%. Draw wiring diagram and explain how to configure DP transmitter and control valve using HART communicator. If the span error at output is 1%, what will be the %opening of the control valve at 60% level of the tank?
How to Calibrate Level Switch in field
How to calibration a control valve?
Explain operation of Haskel pump.