how to install Differential pressure transmitter in gas
line.i need transmitter down side.
Answer Posted / www.islamqa.com
Bharathi is right, we have to use "condensation pot"
# Actually the gas is "self venting" and the instrument
mounting should be above the pipeline in order to avoid
vapor condensation which cuase fault reading.
# For liquid service the instrument mounting should be
below the pipeline as the liquid is "self draining".
# If we want to mount the instrument below the pipeline in
gas service we should use "condensation pot" and the
operator should drain it regularly to avoid fault reading.
# In steam service we use the condensation pot also and it
should be fully filled with water and its mounting should
be in the same pipeline level and the instrument itself
will be below the pipeline, this link indicte the situation:
http://www.eng-tips.com/viewthread.cfm?qid=166893&page=97
the aim of water filling is to provide a solid motion
transfer in order to have a good accuracy.
Regards,
Ahmed Sabry
Control and Instrumentation Engineer
GPC - General Petroleum Company
CELL.: 00 2 0121367310
| Is This Answer Correct ? | 14 Yes | 1 No |
Post New Answer View All Answers
What are the types of control valves available
can any one tell me when ongc placement test and its forms is available????/ pls tell me if u know
We Have Two Field bus Pressure Transmitters of Different Sensor Range (I.E One is of Lower range and Another is of Higher Range).Is same Process Line. My Question is Can i provide Saturation Limit to my field Bus Transmitter as We can provide Saturation current limit to HART Instruments. As During Low Pressure Both Working OK ,But During High Pressure, transmitter with Lower sensor range Goes to Fault mode as Beyond its Sensor Limit it can Measure, So may I provide Saturation point Some where to Suppress This Fault during High Pressure.
WHAT IS THE CAM POSITION IN CONTROL VALVE POSITIONER ? WHY IT IS USED?
What is zone,loop/fire alarm system?
What is profibus?
how can i check vortex shedder bar it is ok? if there is ohms condition are shown correct?
what is the input to be given in digital flow meter during the the calibration time?
what is gas metering system? gas chromatograph? and gas compressors?
what is the difference between magnetic flow meter and mass flowmeter
How to calibrate displacer type level transmitter (chemtrol make )for level measurement in hotwell , LP & HP heater ?
Why does a pressure gauge installed on reactor, doesn't have any vent line below to release the pressure? Is it any kind of designing mistake or it actually does not require any vent line? And if it does not require any vent line below it then how we are gonna release the pressure built inside the pressure gauge?
Why plc require in analog input 4-20amp & 0-10 volt?
Good evening all I need a small favour regarding reliance paper i wanna probable sample papers(e&i) of reliance. if any of u have any idea about dis then plz mail me back.i belongs to electronics and instrumentation engg.so i need e&i papers. thanking u....
i want formula for flow control.am doing project in flow control using orifice . i know value of the flow level(Q) . upstream(p1) pressure, orifice diameter(Do) , pipe diameter(Di) and oil viscosity(Vi) how can i calculate downstream pressure