There are two nos of 33Kv/11Kv 5MVA transformers conecting
through HT cable from substation having metering at
substation itself.One transformer used at a time another
remains stand by.Further 11 nos of 11Kv/440V transformers
are attached on it and each transformer is having its own
Power factor correction panel.Now one 33/11Kv transformer
at no load condition/Stand by condition is having power
factor in leading side upto 0.21 and while when another
tranformer at same situation have power factor in lagging
0.42. Now one thing is clear that transformer one is having
1.5 Km long 33kv cable due to that PF goes in leading side
and another is having only 250 mtr length remains him
lagging. Now i want to know that how i can maintain the
Power factor at no load/ stand by position though both are
behaving in seperate manner.

Answer Posted / k.prakashchandra

Pf at no load is not to be heeded ,as the magnetizing
current is very low and the ct may not measure it accurately
wrt both magnitude and angle shift

Is This Answer Correct ?    4 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is oscillator circuit?

680


How does a tertiary winding filter harmonic(espcially 3rd one) from entering into load system?

1368


what kvrah y we need to take the readind of that

1562


11KV AND 22KV NETWORK KW CAPACITY IN RING AND RADIAL?

1580


why dimmerstate always connected in star connection? what will happen if it connected in delta?

1573






Dear Mr B C pal...Can you plz. put some light on principle of operation of Z-Ct in conjunction to its use with 1Cx1000Sqmm HT Cables & Directional Ground Fault / Over Voltage Relays...Regd..Parag v K 9899115632

2246


State angle criterion.

658


how ct burden,magnetising current,ratio and knee point voltage are related & derived

1756


what r substations?what r there work?why voltages r incresed and then reduced during distribution of power

1467


What is meant by short-pitched winding?

655


for 11KV OH system what will be typical per KM "R" "L" "C" parameter. for 33KV OH system what will be typical per KM "R" "L" "C" parameter. for 33KV UG system what will be typical per KM "R" "L" "C" parameter.

1966


what is difference between cpp electrical system and refinery electrical system

1738


3 phase induction motor connection star or delta while using ac drive motor is .75 to 5.5 kw

1517


I have finish diploma electronics and five years experience in electrical field in ht service how can i get c licensce or other electrical certificate

1162


why do motors burn out? I understand why adding parallel loads to a power source means more current moves through the circuit, and can destroy circuit elements by overheating. What about when you have a vaccuum cleaner intake flush against a floor, a room fan sitting directly against a wall, or a power drill trying to drill through something too hard?

1590