Answer Posted / kiran kumar cheruku
Volt-ampere (VA) is a measurement of power in a direct
current ( DC ) electrical circuit. The VA specification is
also used in alternating current ( AC ) circuits, but it is
less precise in this application, because it represents
apparent power , which often differs from true power
In an AC circuit, power and VA mean the same thing only
when there is no reactance . Reactance is introduced when a
circuit contains an inductor or capacitor . Because most AC
circuits contain reactance, the VA figure is greater than
the actual dissipated or delivered power in watts. This can
cause confusion in specifications for power supplies. For
example, a supply might be rated at 600 VA. This does not
mean it can deliver 600 watts, unless the equipment is
reactance-free. In real life, the true wattage rating of a
power supply is 1/2 to 2/3 of the VA rating
The VA figure is nominally 1.67 times (167 percent of)
the power consumption in watts. Alternatively, you can
multiply the VA rating of the power supply by 0.6 (60
percent) to get a good idea of its power-delivering
capability in watts.
| Is This Answer Correct ? | 24 Yes | 4 No |
Post New Answer View All Answers
What is value of earth resistance required for substation and equipment earthing and what are the reference guidelines
i want to know how to determine that a surge arrester work properly in 11kv system. and how to test a 12kv surge arrester
how to copy from plc ge fanuc versamax series,all input and output, adress, and printout.
What are gain margin and phase margin?
I have 2500KVA transformer delta/star,13.8KV/380V provided with LV 4000A breaker. Already I have 2300KW motor feeder with a full load 90%. Is it possible to connect another 1600A from that breaker? If so how the calculation is done?
What is the need of earthing transformer for delta side of a transformer. (Think of a line section between a star/delta transformer at a grid substation and delta/star transformer at a village. An earthing transformer is there at the delta side of the star/delta transformer at grid substation). As there are no ground reference there will not be fault current if a one phase is grounded. Further L-L phase will be sensed by the primary side of star/delta transformer as a L-G fault. So why an earthing transformer is required at delta side
How can we increase fuel-power ratio of any DG set?
Draw the wave shape of armature current in a generator subjected to a sudden three phase short- circuit at its terminals. Define various reactance of generator from this wave shape.
What is trip and closing coil in cb? Why need of them
what are all types of cross section in AC cables?
How to calculate the size of earth cable to earth the neutral of UPS ?
132/6.6ππ πππππππππππ πππππππ πππ πππ πππππ πππ πππππππππ. πΈ'ππ πππππππ πππππππππππ ππ 6.6ππ/415π πππ πΈ πππππππ πππππππ ππ ππππ πππππ πππ ππ ππ 13/6.ππ πππππππππππ?? πΈπ π½π.. ππππ π ππ’??
If any HVDC line is going with positive & negative(the negative usually have return path of current with earthing electrode). Now the question is if this HVDC earthed electrode which is using as return path and earthed any nearby 400kv or 220kv AC substation equipments. which will be the impact of this on AC substation & its equipment, how severe may be this and what should be the minimum distance require between HVDC earthed electrode and AC substation equipments? It's really an high engineering level question...Dare to answer and increase your knowledge.
Hi, Next week Iam appearing RRB exam for section engineer. So help me to get modal question papers for this position. Iam very thankful to you. Whether question will be fully techanical format or general form. Please give me a details regarding this exam.
why do you add the load short circuit impedance when considering short circuit amperage. It seems that you should only consider supply. If you need to consider loads and you don't know what loads are to be added , what would be a good sub-transient reactance rating for the loads?