generator(Deutz 550kv)is runing for 2 hours with load of
900 amp and then it goes in shutdown with alarm fault
messege of speed fault although heirtz reading fixed at
50,what does that mean

Answer Posted / k.prakashchandra

Gen voltage can not be 550 KV which I think ,is the tr
voltage. Hz is at 50 even after gen has tripped.That
means ,it was connected to grid.The gen might have tripped
on over speed due to load throw-off. If not, speed sensor
of the gen is to be checked

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is cut-off rate?

753


How to calculate earth fault current for 6.6 KV , 50 HZ , 756 Amps , 3000 RPM , 0.8 PF generator

1602


PLZ SEND ME SOME UNIQUE PROJECT OF ELECTRICAL ENG (B.TECH)

1509


What is the best thing to protect the motor from running over full current. CT or O/L or pressure transducer at the given pressure rating

1016


What do you mean by reach and reach the point of the relay?

789






i ha done my 10th with 71% ,ITI with 81% 11th with 75% 12th 43% apprentiship with 71% in SAT i secure 1390 ,TOEFL 27 i was refused four times and in all me interview visa officar told that i am not Qualify for study in USA but i completed my 12th yes i got low persentage in my 12th but i seen to much student they already got visa with them 3 or 4 backlocs so why they are refused me ?

3047


What is servo motor and what are the applications of servo motor?

2250


What is the difference between Static and servo controlled voltage stablizer?

1628


what is conductor copnstant of ab cable

1308


How to arrange a hous hold earthing system to keep minimum earth resistance( below 7ohms).

1479


Why reactive power is needed in a power system? How is it being absorbed or delivered by alternators? For reactive power control we are changing excitation but reactive power absorbing or delivering related to stator. How these two are interlinked? i want a detailed explanation with necessary expressions and figures?

1389


what clearance required for 4.5 mva dry type transformer?

1610


What should be setting for alarm,tripping and cooling fan on for power transformer's oil temp. and winding temp. indicator?

1441


What is the IS standard for MCCB to be use (As per capacity of AMP)& for ACB also.

1566


Actuality I have at home electrical panel with 220v 50hz, and I want to converter from there to 110v 60hz, to wiring on the half of my house. Also I like to keep another half of my house with the original 220v 50hz. What is the best and safety way to do?

1343