We in my plant one of the transformer showing neutral to
earth voltage is 22V how to solve it
Answer Posted / k.prakashchandra
Disconnect earth and measure voltages between phases and
neutral on some load.If the voltages are not equal there is
a loose connection in the star point.Before doing
this ,check the earth connection at neutral bushing.
| Is This Answer Correct ? | 7 Yes | 0 No |