If I have a motor of 1 MW with 6.6 kV, running at 35% load,
how can I save energy without reducing the load?
Answer Posted / k.prakashchandra
You can not lower the load ,capacity, and voltage. To save
energy ,you are left with only reduction of line current to
lessen the I^2R losses.The pf of motor is highest at
full ,or nearly full load.At 35% load ,the pf is less and
hence, the line current is more than required to take the
load (HP)
Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
How to calculate Ith (I thermal) for curent transformer
What will be the current if the resistance total in a series circuit doubles?
how to know the diffrential relay setting of 06mva step- down (delta-star)transformer?
What are the factor to be consider for CT selection in 132kV substation?
salam,hi, i need to know what the spesification of 300amp msb...
Currently what is the highest capacity (MVA) of SPPg generator available in the market?
I am designing new project sub station with 220 kV / 11 kV, 40 MVA capacity. This project have many recifier sets, which can generate 3rd harmonics. Now I have to select vector group of This transformer. To minimise 3rd harmonics, what care should I take in selection of Transformer Vecrtor group? If it is Y-Y with open Delta tertiary then what should be the rating & voltage of Tertiary Winding?
What are the effects of electrical faults?
how we calculate torque ? how we improve it ?where torque will either motor or generator ?
What is the implications when 600 hp motor is started when the unit is running with Transformer of capacity 1500 KVA and DG set of 1000kva
ACCORDING TO IEC WHAT SHOULD BE THE MINIMUM HEIGHT OF G.I. STRUCTURE OF CT, PT, ISOLATOR, LA?
why should the lowest unit of a testing transformer ( cascaded transformer ) have higher power rating??
what is meant by CT`s saturation ? Can we use Metering CT`s with Protetection CT`s ?
How does the slip regulator works as a startor
What are the different types of LT Cables?