Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

what is the minimum dielectric stregth of transformer oil.

Answer Posted / irfan ahmed farooqui

For a new insulating transformer oil(called virgin oil),
the,
value is 70kv for a good satisfactory level but, where as
oil in use (called in service) has values ranging from 25
kv to 50kv , depending upon various factors like ,running
hours of use, impurities, moisture content, sludge content
etc, but it is advisable to discard old oil, if value does
not improve after dehydration and filteration above 60 KV
in laboratory setup or the oil has not passing a
compatibility/mixibilty test with new transformer oil at
different ratio to come to at par in usable ranges as per
standards, on the other hand the exact values and correct
figures for Virgin oil are available in IEC-60296 AND for
oil in service there is a complete guide and specification
available as IEC-60247 where all the nesseccary
informations are available,including the test methods and
apparatus required.

Is This Answer Correct ?    8 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

can we synchronize star system generators with delta system transmission line ? and how ?

2816


I need the list of Universities who have summer intake for BS degree in Electrical Engineering.?

2021


What is main cause of cable's terminal point burned in Lug on high temperature although lug and cable selection is ok as per stantard and also tightness is ok as per situation. so please take in deep and tell correct answer thanku.

8251


what is the isolation transformer. what is the isolator?

2054


define reflection method?

1925


which one is more efficient, torq, power & ecnomy with the same frame size AC motor / DC motor?

2165


Define ampere

1266


300m long and 30kw inductive loade 3phase supply how many size cable required

1412


what is meant by motor startup supervision & motor load jam protection ?

5985


what is the acceptable limit value for Desolve Gas Analysis/

1959


How the capacitance og capacitor volatage transformer is decided?

1951


what is JE exam?

2131


Give some example of fault limiting devices?

1331


what is the role of transistor in Circuit?

1162


In Power cable specification what is U0/U and Um.

3772