We are having Chemical earthing pit
the voltage between neutral to earth showing 22V how to
solve that
Answer Posted / k.prakashchandra
There is a loose connection in the neutral conductor before
the point of testing. whenever there is a loose connection
in the neutral wire, the neutral point gets shifted to the
point of loose connection.
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
I want d.g.set our company
what is PDU in transformer?? which company manufacture??
what are the difference between AC lamp and DC lamp
why motor range is available 22kv,30kv,37kv,45kv and so on? why motor range is not available 21kv,24,25,26,27kv and so on?
what is meant by impedance & transient protection?
comparision between ACB and VCB
What are the characteristics of negative feedback?
what is a bus post insulator? explain its application in a substation.
What are the types of transformers according to the arrangement of iron cores?
Why the efficiency of generator is more than motor in swinburne's test
Can we use shunt trip coil instead of trip coil with protection relay for protection?
I want to design a heating coil of 80/20 nicrome for 3.5KW please give me the calculations choosing for physical dimensions assume coil voltage will be 110V AC assume necessary conditions
what happend to DC shunt motor if its field winding insulation becomes slightly weak? will that motor can run on full load or not explain in detail. thanks
what is the earth current,reverse power,electrical trip generator short circuit,low voltage, high voltage please discribe me
What is the reason for using a GE G101 MCB in place of an EP102 MCB if both are capable of AC circuit protection?