if a 3phase motor runnig in star delta starter with full
load of its,and its rated 15 amps.now we conneted over load
thermal relay at its main contactor,here what will be our
amps sittings?
Answer Posted / pillay
If star delta connection it will have 6 wires . so the amp setting of the TOR WILL BE FULLLOAD AMPS /ROOT 3
15/1.732 =8.6 AMPS
| Is This Answer Correct ? | 6 Yes | 2 No |
Post New Answer View All Answers
Power factor =1.000 at factory in supply. However, PF = 0.8 at motor end. Current = 100 Amp, Voltage = 400 V. What is the power distribution loss? Can I reduce it by adding capacitor at the load feeder?
What are the advantages and disadvantages of closed-loop control system?
How to test IR testing & magnetic balance test
What is the meaning of HT Trivector Meter ?
1600 KVA ka transformer hi aghar lt side par 800A aur voltage 420 ho to HT side ki cable ki rating keya ho gi?
what is the effect of power factor of machines in starting current
what is the IEC standard for Power Cable installation in onshore (like in direct buried ground or above groung)
What are the difference between CT/PT operated Meter and RRAMR Meter for HT/LT application?
EHV current carrying parts need to have smooth finish,then how can a 245kv GIS with emery finish can run so long?
How many types of circuit loads are there in a common electrical circuit?
difference between high and low impedance BUS BAR relay??
In Designing the rating & accessories of a MCCB how to choose the type of releases..means what is the basis for selecting, thermal magnetic, electromagnetic & microprocessr based releases
how the synchronizing is obtained at bus couplers in grid substation? (because there we cannot change the frequency in one of transmission lines like in generator synchronization)
explain different types of d.c motors?
Work done in a free expansion process is