1)what is hypo test. 2) which cable need to hypo test.3)
when hypo test can be done before or after glanding.4) what
is the purpose of hypo test.
Answer Posted / mukund
high potential test carried between line-line, line-
neurtal,line and neutral to graund on any control panelto
check insulation between live conductors and enclosure body
at hv like 1.5kv and onward depands on system voltage and
local standard, it is carried out also on control wiring too
e.g. from 300 to 600v it need 2.7kv test for 1 second and
2.4kv for 1 minuts,note when this test have to do test job
must disconnected from line voltage,it is most likely
megeer test, after testing it need to discharge tested line
to graund
Is This Answer Correct ? | 37 Yes | 7 No |
Post New Answer View All Answers
in HT service 3ph 4 wire service Y-phase voltage shows zero . whether it is meter fault? or what be the reason ? if y-ph voltage zero ,can current is recorded? reasons for failure?
Why does inductive loads consume KVARs?
What is trip and closing coil in cb? Why need of them
What is Phase margin?
Inductor and capacitor........power in one phase and ...... in it another phase.
what will happen if there is a voltage leakage or current leakage in an electrical train
How we calculat the NGR of 3phase Generator, Our generation voltage 11KV
What is the RMS and DFT principle of analogue maesurments. Which way they are advangages. where which princples give optimum results.
what do u understand from filter factor of reactor?
why do motors burn out? I understand why adding parallel loads to a power source means more current moves through the circuit, and can destroy circuit elements by overheating. What about when you have a vaccuum cleaner intake flush against a floor, a room fan sitting directly against a wall, or a power drill trying to drill through something too hard?
what are the ''pitting rings''and how cn they be controlled in a series generator
How to calculate the heat load for a electrical room
what happen if generator of micro hydro running at only a small percentage of its capacity, as a comparison, if the diesel generator that runs on only a fraction of its capacity there will be a wet stacking
Is there any question in the name of Static Switch in UPS??
How to Decide the Location of Earth pit for Compressor in Oil Depo? and How to measure the resistance of earth pit Pls explain me with the help of Circuit Diagram?