What are the possible causes of REF operation on a power
transformer
Answer Posted / k.prakashchandra
All cts(Phases and neutral) are connected in parallel.If
there are unbalanced currents in phases, the resultant
current in REFR is zero as the difference is also measured
by NCT .If there is an earth fault inside the transformer
or between cts and bushings ,the fault current is sensed by
NCT only. Hence current balnce is lost in REFR resulting in
trip command by the relay
| Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
why we use four type of phase angle difference between pimary & secondry winding of a transformer & where we use them?
What is kvar?
How to do stting of vl250 siemens MCCB
700KW 6.6KV slip ring induction motor to use VFD to control the speed
Explain Active power,reactive power,how its related to each other , & inductive ,capacitive.
what is vtg limit of earth and neutral at transformer side?
xfhnchncv?
How to check the Bushings of the transformer?
there is an alternator 480 k.w, 400v,50hz, 4-wire running on load having leakage alternator body earthed current 38 A. is it within acceptable limit? if yes then give reference if no then how to bring within specified limit
what is the ground fault relay,which purpose it will be use,clearly tell me plz
The 3 phase Delta connection RB=440V, BY=350V,.......* is Line to Line voltage RY= ? And Formula....?
What is the difference between voltages or potential difference? And what are they?
pls tel me the electric train traction motors name plate details like rpm,torue,voltage,amps,watts..ect..
if voltage bt phase & nutral is 38v in a panel board . whats the root cause.
how desiel generate sart fail of eb?