What are the possible causes of REF operation on a power
transformer
Answer Posted / k.prakashchandra
All cts(Phases and neutral) are connected in parallel.If
there are unbalanced currents in phases, the resultant
current in REFR is zero as the difference is also measured
by NCT .If there is an earth fault inside the transformer
or between cts and bushings ,the fault current is sensed by
NCT only. Hence current balnce is lost in REFR resulting in
trip command by the relay
| Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
There are different classes of protections in power plants.class a,b,c are clear..is there any class d and e r there..and elaborate class b protection.
can someone explain that how the speed of the protection system affects the fault level calculation?
How to Calculate the Fault Level of Electrical Installation
How does PLC work for sychronising of Two or more DG sets?
Do any one know exacatly when the results for NHPC held on 8th march 09 for engineering trainees will be released ?. if so please post it, i'm eager to know it.
how to modify DOL control panel into Delta Y connection?
What is the function of probe in cro?
3 phase Motor will be given 2 phase after 2 to 5 second we given 3rd phase so Motor Run sum-time in forward or sum time run reverse direction. All time phase sequence is not change. Why motor run in reverse direction? Please Explain........
what is difference between cpp electrical system and refinery electrical system
What is the operating principle of turbo-generator.
What is the loss of power of transformer 220kv/33kv,63/80mva of % imp12.05 at 80%load
How to arrange a hous hold earthing system to keep minimum earth resistance( below 7ohms).
FEINGING DECREASES THE FLUX DENSITY IN THE AIR GAP. HOW?
What are the properties of a resistor?
I COMPLITED MY B.TECH AND 10TH CLASS WITH 70%MARKS BUT 12TH CLASS 55%MARKS..CAN I GET INDIAN RAILWAY RECUREMENT EXAMINATION?