Consider a level troll.
i am getting a correct value in 4mA and 20mA.
the value in the middle(30 to 60%)is disturbed and i am not
getting the appropriate value.
what is the solution to normalize the level and to get the
correct value..

Answer Posted / joe mccabe

a) calc the hyteresis and reset the 4-20 to it, accepting
the deviation in the middle

b) test the amount of deviation @ 4ma,8ma,12ma, 16ma,&20ma
and see if slope is repeatable, write program correction
for slope

c) Your instrument has a hardware issue, do the right thing
and replace it.

Is This Answer Correct ?    6 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

A valve in series with an orifice plate (DP transmitter), is aligned for constant pressure in the pipeline, if there is an error dx, How to align it in process.

866


how to rectify the poor signal strength in utrasonic digtial flow meter ,model:ge digital xce868i

843


can any send me a forbes marshall dtron 316 manual

1470


When doing a liquid seal on a differential flow transmitter , most of the time the sealing liquid will be heavier then the process fluid. For wich application will the sealing liquid be lighter than the process fluid if transmitter is mounted below the process line.

1399


What are the uses of orifice plates?

618






where proximity sensor installed on tank in loading arm application

1524


what does it mean an active front end in vfd plz explain it briefly

1403


we are using centum vp as monitoring with Dell precision work station T3600 but some times PC(s) are restarted automatically . how we can solve this problem? thanks

1762


it is possible to check the fail safe condition in pressure transmitter. if possible how?

893


Why we are using reverse action in displacer types level transmitters on some Vessels?

2033


can anyone guide me how to get any of the previous year GAIL question papers? are they available? 0n 2nd august i have to take the written test.

1463


Sir, I want junior executive, Instrumentation question papaer for IOCL, Plz send to arabinda.ghosh83@gmail.com

1689


Instrumentation Safe Guarding test. How to determine the interval time of the test. eg:Halfyearly,Every year,Every three years etc.

1645


How to Calibrate Vortex Flow transmitter in field

767


How digital input and digital output 's are working in dcs

2036