Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Consider a level troll.
i am getting a correct value in 4mA and 20mA.
the value in the middle(30 to 60%)is disturbed and i am not
getting the appropriate value.
what is the solution to normalize the level and to get the
correct value..

Answer Posted / joe mccabe

a) calc the hyteresis and reset the 4-20 to it, accepting
the deviation in the middle

b) test the amount of deviation @ 4ma,8ma,12ma, 16ma,&20ma
and see if slope is repeatable, write program correction
for slope

c) Your instrument has a hardware issue, do the right thing
and replace it.

Is This Answer Correct ?    6 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is temperature compensation?

5406


In turbine what does term CDP, NH, HSSOC means.

1747


Which tank weighing system is better to install (Accuracy point of view) 1) Tank weighing system with 3 load cell or 2) Tank weighing system with 4 Load cell

1291


What is motion balance principle?

1153


can anyone tel the syllabus or previous year question paper for BHAVINI(EIE)2014.

2422


In turbine what does term CDP, NI, NH, HSSOC means.

2552


why is not useing in boiler skin thermocople

5246


Specify eight technical requirements that you would consider important, when deciding upon a particular control valve?

1867


How to find out the current of two motors having same power consumption but different RPM?

1989


hi! i want to know about mpse exam.

2268


how to rectify the poor signal strength in utrasonic digtial flow meter ,model:ge digital xce868i

1236


how works encoder in plc

2050


We Have Two Field bus Pressure Transmitters of Different Sensor Range (I.E One is of Lower range and Another is of Higher Range).Is same Process Line. My Question is Can i provide Saturation Limit to my field Bus Transmitter as We can provide Saturation current limit to HART Instruments. As During Low Pressure Both Working OK ,But During High Pressure, transmitter with Lower sensor range Goes to Fault mode as Beyond its Sensor Limit it can Measure, So may I provide Saturation point Some where to Suppress This Fault during High Pressure.

1640


Programmable Logic control.

1934


How many are the types of instrument cables in terms of No. of pair.

2173