oil sample dielectric test gives the insulation rupture
voltage at 26 kv. is this transformer safe to be operated .
The working voltage is 11 kv
Answer Posted / k.prakashchandra
40 KV is the minimum value required. You need not panic.
Measure the BDV again after 15 days. If there is drop ,oil
filtering is to be done at the earliest
| Is This Answer Correct ? | 1 Yes | 1 No |
Post New Answer View All Answers
what is the meaning of 0.5ohm Resistance
Distribution transformer we provided 2 separate earthing pit for Body and 2 separate earthing pit for neutral,we can not connect separate body earthing pit to other earthing pit but we do metal glanding in secondary side cable termination in both side, transformer and PCC panel (LT Panel), is this safe for transformer and other equipment?
How eddy current generation support the idea of train braking?
WHY CBCT USE ONLY IN Y PHASE NOT OTHER PHASES
Explain what is electric traction?
What is George phenomena to start the synchronus machine?
what is meant by 3rd hormonics ?
what type of questions are asked and howmwny questions belong this catagory?
Can Anyone Answer anyone of these ? Q1) why direct SOLUTION of Load Flow Studies in Not Possile ? Q2)Why majority of Buses in power system are load buses Q3)Why one of the buses in Power system is taken as reference bus (slack or swing) Bus ? Q4)Bus Admittance Matrix is a sparce (means it contains some zero elements ) matrix , give reason
why electronic instruments is more favorable than electrical?
What type interview questions ask in Electrical technicians
hai now i am working as a electrical design engineer in construction field can i get a job in oil and gass field or power plant project as a electrical design engineer?
what is the size of cable for 15kw motor and 85 meter cable length using with vfd
what happens in the short circuited secondary transformer,if the resistance of the short circuit is increased gradually?
1sq mm dc powr cable can carry how much dc currnt