Answer Posted / nagendra
To completely eliminate the malfuntion of AVRs(that are
being fed from generator terminals through excitation
transformer) due to load fluctuations on the alternator
Permanant magnet generator is a solution.PMG wil feed to
the AVR giving AC output,which wil be converted into DC and
wil be fed to the field winding of the AC exciter of the
main generator(but not to main generator field).Finally AVR
controls the exciter output (by varying its field
voltage).Exciter output wil be directly connected to the
main generator field through rotating uncontrolled
rectifiers.
| Is This Answer Correct ? | 19 Yes | 3 No |
Post New Answer View All Answers
What is pd controller?
what is mean by transition resistance of transformer?
In HVDC LINE RECTIFIER CONTROL ON CONSTANT CURRENT AND INVERTER CONTROL CONSTANT EXITATION ANGLE CONTROL BUT HOW INVERTER CONTROL CONSTANT CURRENT?
Can we use both Electrical & mechanical interlock between tow breakers? if yes how, please explain
What are the two basic types of transformers?
area control error
Why do we apply both Differential and REF (HV and LV) protection schemes on YNyn configuration of a transformer?
How many VSC based HVDC are there in India and the world
An 8 pole, 50 Hz, 3-phase IM is loaded to a poing where pull out torque will occur. The rotor resistance per phase is 0.3 ohm and motor stalls at 650 rpm. The slip when motor stalls is A 1 B 0 C 13.33% D 10.33%
What is the different between conventional MCC and intelligent MCC? Common controller or controller for each bucket
What technology is used in latest generators?
What is the general power consumption rating of CPU CRT type and Flat type, Monitor,Printer, projector, Scanner?
how net resistance islow in star connection and viseversa in delta connection...? if anybody could explain in detail it wud be helpful.
placing earthing pit in pathway is correct or wrong??. placing earthing wireGI1/18 inside walls is correct or wrong?. explain!!!
what are the condition that makes hooter blow?