Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how to choose the cable rating for load (KW)? EXAMPLE.50KW load

Answer Posted / m.saad

Calclate the load Current
I = p/((root3)*V*P.F )
where I line current, v line voltage
then go to cable tabe
and check the Drateing factors.such as
if this cable underground,free,soil,depth of laying,
ambient temperture, armoed or unarmoed etc.

then calcute the voltage drop
if more than 4%
you should to select the next bigger cross section at table.

by experince for copper PVC cables
1mm take 2.5 AMP

Is This Answer Correct ?    32 Yes 13 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Main advantage of auto transformer over two windings transformer is that A it needs no cooling B it uses only one winding C core losses are reduced D it has simple construction

2988


What are the common sources of energy?

1170


What happen if we apply square wave or traiangular waveform voltage to the transformer primary winding instead of sinusoidal wave?

2236


What are the limitations of Kirchoff's laws?

1644


how do u gauge the size of the cable ?for eg. consider a 300 sqmm L.T Cable.How do u determine the size of the cable seeing it pratically?

2166


Draw transformer phasor diagram.(full load,no load)

4223


What is critical disruptive voltage?

1376


Is it required to lay 2 runs of GI wires along with armoured cables from one power DB Machines of higher rating?

2101


we have amp, voltage, kw, length detail then how to calculte copper & alluminium size of conductor of 3-phase induction motor

1518


I HAVE BEEN SELECTED FOR APGENCO A.E(ELECTRICAL) 2008.HOW MUCH WEIGHTAGE FOR INTERVIEW AND WRITTEN TEST.HOW I HAVE TO PREPARE. PLEASE GIVE INFORMATION IF U KNOW.WHAT ABT G.D THIS TIME.CALL RATIO 1:2

2968


WHAT IS THE FUNCTION OF SHORT CIRCUIT MAINTENANCE CT

2505


it is possible to rotate the DG engine dc starter with wrong polarity connections? why?

2311


Can i use the B-curve MCB instead of C-curve MCB

2081


What is VCB? where it is installed at SP. What is SP?

2244


can i use 2000/5A Clamp meter to measure HT cable

2076