We have a 33/11kv switchyard having 12.5 MVA power
transformer. We export & import power through this
transformer. When we export power, the PF will be depend on
GRID PF & when we import power the PF will be depend on our
load PF. but the problem is that,when neither we export nor
import but our 33KV vCB is in close position,our meter read
the power factor 0.14 to 0.25 at that moment. So how can be
we improve the power factor at that moment.
Answer Posted / k.prakashchandra
You should realise that when there is no load on
transformer, the pf is almost zero
| Is This Answer Correct ? | 2 Yes | 1 No |
Post New Answer View All Answers
would you please give me any idea about the BARC interview question on electrical? i have an interview on 1st july.....plz hlp me.......its urgent......
What is cathode ray oscilloscope (cro)?
12.5 tons a/c is their how much kva generator can recommend to the customer.
what is the minimum requirement gigaohms for the insulation test using 5kv in 300mm xlpe cable
Why auxiliary transformers are not connected in parallel in primary stations?
How to calculate ant test the burden of Current transformer
How you calculate the repturing capacity of a HRC fuse
how can found motors folt current ? how can disided circuit breakers caoicity and breaking capicity ?
Define cut-off rate?
How to do stting of vl250 siemens MCCB
how electical engineer is related to apsrtc (general) post? if they ask a question in interview as why did u choose this job what shd be answer
what is integrated ac contact circuit
What is reactive power and where it is used.
please tell me, how i clear the objective test? when i studied form the one book after i solved the objective ,that time i solved that qes. but if i tried solve objective form the other book then i could not solved these que.
why the electrolyte level in lead acid battery is maintained 2.5 cms above electrodes?