Answer Posted / s vedpathak
Control valve is used in close loop control system.If it is
hunting , then to troublshoot first put loop for few sec in
manual mode, still if v/v is hunting then it is field
problem i.e v/v or I/P converter problem.
If it is not hunting in manual mode, then the problem can
be either the loop process variable(PV) is hunting or if PV
is ok, either the load/process is varied or loop needs
tuning.
Is This Answer Correct ? | 57 Yes | 1 No |
Post New Answer View All Answers
What is cut off relay? And why use in PLC and DCS?
what is o2 analyzer and how it measured ,what is the role of this analyzer in cfbc boiler...
Why use ball valves on Gas pipelines instead of gate & or globe valves...means basic diffrence or use of these valves..how designers knows this type of valve with rating is required...
What is the difference between conductive lined pipe and conductive unlined pipe? Why do we see that?
How RAL(Rotary air lock)works in cement industry?
NPN transistor, SCR, Zener diode, LED, Varactor diode, Vortex meter, RTD, Resistor, Crystal
what is a vortex flow meter,mass flow meter and electromagnetic flow meter.particular use of this.means in which condition particular meter is used.
what is stroke check for field instument transmetter's & AOV's
WHY THE DEGREE OF VALVE PLUG AND VALVE SEAT IS SLIGTLY DIFFERENT I CONTROL VALVE TRIM DESIGN
Describe the functions of the Operator Interface including the considerations related to alarming and display layout/configuration/layers.
Isometric drawings are generated during _________________ phase of a project
what is difference between fork type and capacitance type level switch. where it is using
how u choose thermowell lenght n pnumatic C/v size?
what should he know if he is an assitent engineer instrumentation in cement industries of experience of 10 - 15 year.
what is the current pay package for an instrumentation engineer having 2 years of experience in cryogenic technology???????