how to claculate earth strip size for 1500kVA transformer
for neutral and body
Answer Posted / bala.a
you will follow as per State electricity board norms - 50
x 6 mm Cu for Nu and 50 x 6 mm GI FOR body 0r
you will calculate as per short circuit calculation
Formula 0.0054 x root t x I
Where
t =1 second
I = SHORT CIRCUIT CURRENT
example
Fault current- 33kA( assumed )
0.0054 x root 1 x 33000= 178.2 mm
so you will recommended 50 x 4 mm Cu
| Is This Answer Correct ? | 14 Yes | 9 No |
Post New Answer View All Answers
How to calculate no of EARTH PIT? Describe the formula as per IS standard?
If a 3 phase induction motor is in off condition in the conveyor and rotor of the motor keeps moving with the conveyor than the resistance of windings of motor varies. why is it so ??
which model T or pie model is prefarable in power syatem
What are reasond for high wattage in single phase induction motors
1. If 8.35%Z means the percentage impedance of 132kV-line from power company, we will like to confirm its base capacity?
how to determine the cable size...pls explain me with the formula taking particular load....does the factors like impedance & short circuit rating influence the cable size, if so how....
What is the difference between PS & metering CT (5p20,0.5 etc.)? Why in PS class CT only Vk is given ? Is PS class CT is more accurate than metering CT?
What happened ,If 3 phase clearance not maintained in 33KV Line,11KV LIne etc?
In general bus riser follows the bus section in SWGR. What are impacts if bus section follows bus riser?
what is the diff. between x'mer , isolation x'mer & ultra-isolation x'mer ?????????????
how the CT and PT is connected in the circuit during testing of transformer explain with diagram
what is the difference between STAR and DELTA connection and application wise how it can be utilizedd
what is the synchronous timer ? and it applications.
how was your last weekend.
In diesel generator how AVR get voltage to excitation. And basic diagram DG EXCITATION CIRCUIT.