in three phase with neutral connection, what will happen,if
the neutral is in open condition with single phase
distribution panel

Answer Posted / pillay

It depends where the neutral is in
open condition.
when all three phases are loaded with
single phase load and the main neutral
is in open condition than the voltage
across the load will vary according to
the load and the voltage can be as high
as phase to phase voltage thus resulting
in damage to electrical equipments, but
if they are loaded symmetrical than the
phase currents are balanced internally
and the voltage across the phases are balanced.

Is This Answer Correct ?    2 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what r PID controllers?why they r used?what is there purpose?plz Explain in detail

1620


Calculate torque developed by the 3-phase, 5 H.P., 4 pole induction motor runs at 1500 rpm A 23 N-m B 21 N-m C 10 N-m D 0 N-m

4351


What is Icu and Ics and what is difference b/w them. please tell me how to calculate a size of a copper bar for a system or a breaker... reply on... king.arish@gmail.com would be waiting for a logical answer.

1932


Explain the working of variable frequency transformer?

651


why zero sequence impedance measurement is not applicable for single phase GT

1697






Why do we avoid electrical conduits in floors at apartments?

1623


solar inverters was not connected to the nuteral link .this nutwral possible to any other systems

1349


when qty of cable being purchased is not sufficient according to the standard,what should the inspector do to ensure its quality according to the standard?

1530


Is RTCC panel needs any control supply.

1498


What would cause a 240v choke that should give 110v out on a 16w lamp to gradually increase to 160v?

1745


How to calculate main incomer rating of APFC Panel ? Let's say i want to find main incomer for 11kV, 1000kVAR Panel.

1231


Logic using 1 kV or 1,1 kV grade in house wiring Low voltage cable. Explain/suggest? some use 1kV and some prefer 1.1kV grade insulation low voltage cable why??

1213


Pl.brief me about Electrical power distribution system from Main generating station to Industry.What is the use of in between station.

1592


I HAVE A INCOMING 100A MCCB TPN 25KA, CABLE LENGHT OF 80M 70MM CABLE SIZE FROM MAIN SUBBOARD TO NEW DB.BASE ON THE FAULT LEVEL SETTING OF 45KA.I WOULD LIKE TO FIND OUT 25KA ENOUGH KA. APPRECIATE IF SOMEBODY CAN ASSIST ME WITH FORMULA FOR THIS. FRM: JEFF

3516


ANY ONE TELL ME ABOUT generator synchronization panel panel to synchronise 3 gen of 250kva both automatic and manual. 2 gen output vol 415 3ph, 1 gen output vol 400 3ph SEND THE DETAILS DIAGRAM ON THIS EMAIL ADDRESS ayazleo@hotmail.com as soon as possilble best ragrds electrical engineer ayaz mahmood SAUDI TECH

3703