Why we are not using capacitor in line when load on Genset?
Answer Posted / kadiresan.k
whether the load is on EB or DG, p.f to be maintained close
to unity and the type of load to be studied and capacitor
to be connected accordingly. The Capacitors to be switched
ON and OFF according to the load with the help of APFC
panels / Controllers. In case of load shedding time, the
concerned capacitors to be tuned off immediately, else it
will result in over voltage at the system if the load is on
DG side. So the power system to be optimised to handle the
load in both EB and DG with proper power factor correction
systems.
| Is This Answer Correct ? | 2 Yes | 1 No |
Post New Answer View All Answers
When and where resistance earthing is used ? How to calculate the time constant for earth fault
Classify milling machines.
please send me the previous year's question papers of jindal GET exams
BSNL TTA EXAM QUESTION
How to run a three phase motor into single phase........
can anybody tell me that for p.f. Improvment we use capacitor banks but how to decide its capacitance. As we all know how to calculate kvar but what abt capacitance value
wheather the size of windings in motor and generator are the same
Inverter. converter. Ups.MCB.solar.alternators. motors.
I WANT TO know WHICH WAY IS BETTER FOR CONNECTION BETWEEN POWER TRANSFORMER AND MAIN DISTRIBUTION PANEL. 1-IS BETTER WE USE CABLE? 2-IS BETTER WE USE BUS DUCT? my transformer rate power is 2500KVA
The electromagnetic torque developed is proportional to what in a D.C series motor?
In a power conditoining unit (inverter) of a solar plant when we measure the d.c. current fed by different strings of solar plates to inverter, the current in the negative wire is less almost by 1 ampere to the current in its positive wire say current in positive wire 5 A , then current in negative wire of the same string is 4 A. Since the current entering should be equal to current leaving then why the current is noticably less in negative wire.
Generation of voltage for each phase are same of a turbogenerator.Although the short circuit current flow when two phase of turbogenerator are shorted(where current can't flow without potential difference),why?
How to calculate ant test the burden of Current transformer
how can get electrical "c" licence.i am complited in DEEE.PASSING YEAR OF 1993.WORKING IN PVT COCERN LT LINE.PLEASE ADVISE ME .CELL NO 9994786021
why 5kW motor becomes unbalance if its relay trip 1st time and its set value is 7.0 A