How can you calculate in detail the VA burden of current
transformer used for Restricted earth fault protection?
Please understand that the CT required here is Class PX or
X. Also please show the calculations for knee point vtg,
stabilizing resistor, magnetising current.
Answer Posted / william lobo
Knee Point voltage is nothing but a point at which the CT
saturates. Thats why its always better to design the CTs
which can operate without saturation even at a voltage
appears in the CT during fault condition. Pls find below
the following formula for calculating the Knee point
voltage.
Vk=2If(Rct+2Rl).
where, If is the current refected to the CT secondary
during fault condition,
Rct is the resistance of the CT which can be adopted by
means of a thumb rule considering the CT ratio,
Rl is the lead resistance i.e. sum of the resistance of the
wire connected between the relay & CT and Impedance offered
by the internal circuitary of the relay
For PS class CT's designed considering the above,burden is
not applicable.
| Is This Answer Correct ? | 7 Yes | 0 No |
Post New Answer View All Answers
how to set the time in digital timer ?
WHAT IS THE CURRENT CARRYING CAPACITY OF 2.5/3 CORE HI TUFF CABLE,WILL IT SAFLEY CARRY 8.6 AMPS OVER 120 METRES,CAN YOU ALSO ANSWER WITH FORMULA FOR WORKINGS OUT ,THANK YOU 3RDYR APPRENTICE.
A powerplant has 8 gensets operating in grid parallel mode. In one genset sometimes there is pf variation and kvar variation. The plant operates in pf mode. When this variation is observed the load is stable, voltage is also stable, freq and genset speed is also stable. How will you check the functioning of pf card. What shall be the ideal output vdc of the pfc, from there it is input to AVR?
i have applied for junior engineer 2 c&w for Guwahati RRB please send me last five year question paper
sir i ve applied for hindustan petroleum and power grid india ltd..and the exams on feb 22.can you pls send model papers and tell how to prepare for those.i need to get into any of these for sure.....
Leakage current,un balance current which relay using for high voltage transmission?
What is Faraday's law
pls tell me about ups internal connection & we have given only 3 phase supply to ups system how get 4 wire (R Y B N )
how to find the torque of the single phase synchronous motor by doing an experiment
What is expention fastener (Fan)
how to check regenerative load in drived motor
Explain the different regions in frequency response?
Why need 3phase machine double earthing?
Can you please explain creepage distance in detail, for a 6.6kV cable head what must the distance be and how do you determine it?
I have one ct of ratio 3000-2000/1 Amp its knee point voltage mentioned on name plate is 500-333/30mA-50mA at Vk/2. in secondary box there is three terminal named 1S1, 1S2, 1S3 then on which terminal obtained the knee point voltage ie 1S1-1S2 OR 1S1-1S3 & also specify the knee point voltage for the ratio 3000 from name plate.