Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

How can you calculate in detail the VA burden of current
transformer used for Restricted earth fault protection?
Please understand that the CT required here is Class PX or
X. Also please show the calculations for knee point vtg,
stabilizing resistor, magnetising current.

Answer Posted / williamlobo

Restricted earth fault protection is a differential scheme,
with CTs on the transformer neutral and phase leads. The
phase CTs are connected together in parallel & then
paralleled with the neutral CT. The resticted earth fault
(REF) relay is connected across the paralled CT circuits.

The relay is either a voltage operated device (eg Alstom
MFAC14)or a current relay with an external setting resistor
(eg Alstom MCAG14). In either case, the scheme is set at a
voltage based on the maximum voltage that is developed at
the relay for an external fault. A practical setting is
50% of the CT knee point voltage, if full info is not
available.

Is This Answer Correct ?    3 Yes 3 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is the pulse and audio frequency transformer? what is different between induction regulators and tap changing transformer?

2118


What is lighting kitts.

2118


What is the difference between grid and off- grid system??

1962


What is different between Difnit time and instatous over current relay

2554


How may I get the maximum current capacity for a particullar size Alluminum or Copper cable if there is compulsion to use?

1925


How to calculate the size of earth cable to earth the neutral of UPS ?

1947


How can we checked Killo Watts of Motor & Alternator?

2157


What si the d/f b/w KVA & KWH, kvarh & kvar, kwh & kvar phase voltage & line voltage

6169


do you have some of interview Questions in power and genrator section in general whith answers

2186


what is the difference between earthing and unearth

3101


how to differentiate a mpcb,mcb with a contactor? Explain their working operation

2227


Whether it is possible to measure energy at the input of rectifier transformer (12 pulse with very high odd harmonics)

1909


How do we arrive at selecting reactive capacitance value as 30% of h.p rating of motor?

1845


why we cannot protect 100% winding of an alternator by using differential protection?

2259


why star point of HT motor not earthed?

2287