How to calculate earth flat size for 250 Kva DG and
transformer?
Answer Posted / samson
Neutral will come in to picture whenever u start ur DG (
and not paralleing with a Grid as it will create a
circulating current), so worst thing that can happen is L.G
fault on a phase of generator or inside the winding , so
max current that can go is dg rating/ phase volatge ( use
formula above) so ur neutral should be capable of that
much curent ,( neglecting any contact resistance in ideal
case)
the switching of neutral is done through contactor.
use this to size strip
the I = K* A/ sqrt of time ( some of IS standered give u k
for bare conductor) Dg manufacturer will size support for
S.C forces
get k for alumi. or copper u can size to next standered
sizes available 20 x 6, 40 x5 n all
Is This Answer Correct ? | 4 Yes | 5 No |
Post New Answer View All Answers
What is the formuala to calculate the rating of motor protection circuit breaker
define the active power?
actually i can't understand what is 3dB ? and it's really not clear to me.please any one let it me be cleared.
what is an unbalance in acircuit? in a three phase 3wire circuit how an unbalance will come? in a three phase four wire system how an un balance is coming?
how to calculte capacitor range for single phase induction motors??pls tel
what happen when increase or decrease size of lamp,light.glass.
what is difference between elr and R eartl realy.
What is meant by system?
what is EIB lighting control system? what is the advantages of this system?
Is it true online ups having bypass mode if it is true then why we called ups because it is interrupting power when goes in bypass mode
what is the pulse and audio frequency transformer? what is different between induction regulators and tap changing transformer?
How to protect sensitive loads such as Dosing pumps inside a factory from voltage surge/voltage fluctuation.
what is the role and fuction of automatic transfer switch in rotary ups
Why do we need a separate control desk & PLC control panel in Boiler plant or coal handling plant? Can we provide cost effective Control desk cum PLC panel. Is there is an specific need for control desk.. kindly advice.
how to discharge 3 phase power factor correction capacitors