bangalore i have a doubt why we have to
maintain DG power factor in the range
0.78 to 0.8
Perhaps i f it is increased means what
will happen in DG
Answer Posted / k.prakashchandra
Keeping pf at 0.8 lag when running in parallel means the
terminal voltage of gen is higher than the system or busbar
voltage.But it results in higher gen & field currents which
cause unwanted heating of armature and also the field.If
you keep the pf at unity or -ve,the gen does not contribute
to system stability.The generator should also share the
reactive power of the system, which is usually
lagging.Anyway pf may be maintained at 0.9 to 0.95 lag.
| Is This Answer Correct ? | 0 Yes | 1 No |
Post New Answer View All Answers
How can we calculate ac current from the given DC current when AC voltage is given?
Which type of questions well asked. ?
What is the meaning of utility ground and clean ground? How the distribution panel is grounded?
What are the operation carried out in thermal power station?
iam working in power plant. In hot places tube lights are glowing at the end portion only. what is the reason for that?
How REF protects transformer alone? explain with diagram.
At what speed an electric car can run with 2 HP motor of weighing 400 kg?
Pl. give me checklist for installation & commissioning of machine tool.
can any one suggest me the tilt angle of my solar pannel ?? or tell me how can i know the fix tilt angle of my solar pannel?? my cordinates are 31.503629,72.993164.
Testing report of Earthing of 3.15 MVa PTR.
How to Calculate KA Rating of Main LT Panel
Star Delta Diagram with full description
Explain about Dubai electrical sysaem? Explain about Dubai drinking water system? Explain about Dubai Burj tallest building Electrical,Water.etc.. maintenance system?
In Generator How suction compression power and exhaust works ?
Dg pf .71 i am improve pf 0.80 what capacitor connected in dg how?