Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

what is diffential relay? testing proceure?and
transformer reach Over load thet time differencilal relay
operate or not ?

Answer Posted / g.govarthinam

Dear friends
1.Diff relay compares two currents entering and leaving the
protected equipment or zone in respect of current
maagnitude and phase angle, and if there is any unbalance
or spill current found, that current will flow through the
operating coil of the relay and give trip pulse to the
Circuit breaker to isolate the supply to the transformer.
2.Please note that,Diff relay will operate only for
internal fault of the protected equipment(for
example,winding fault in transformer) and it should not
trip for over load of transformer and any external fault.

please feel free to ask further doubts in this topic.
regards
gova

Is This Answer Correct ?    6 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is the diference between the 4pole & 6pole DC Motors & what is advantage 6pole over the 4pole ?

1994


single phase power supply give to separate one steel coup with water, what reaction create

2070


what is the minimum pay scale for electrical engineer (building construction)in kuwait? plz revert back with yrs of experience & pay scale respectively.

2145


why there using acb enclosure in big buildings

2083


What is principle of Floroscent tube 36watt.

2029


In Air circuit breaker LSIG protection unit is used. Without fault in cables (2 runs 3Cx150Sq.mm Copper, 1Kv grade, XPLE armored cable IR value is more than 550Mohm @ 500V Megger) and load section Long time Overcurrent protection is triggers and trips the unit. We changed LSIG protection with new factory tested unit. Even then fault is persisting. Please suggest the possible causes

787


Why 15Amp. MCB is suitable to carry load of 1.5Ton Ac please Explain?

2150


How to do bus bar short circuit calculation for 230KV/11kv, 60 MVA Substation?

4711


Alternator rotor earth fault relay circuit

2055


i want wipro vlsi placement pattern please send me

1758


WHATIS TIME CONSTANT? WHATIS ITS SIGNIFICANCE? ILLUSTRATE THROUGH EXAMLES.

2206


What happen if 200 KVAR capacitor connected to power continuesly?

2116


can any one tell me about the Extra low voltage systems?From where we give supply to these type of systems??

1891


it is possible to measurement of tension of slipring induction motor(SRIM)carbon brushes, any maesuring instruments are available in the markets.

1992


what would happen if reactive power (kvar)is increased (more)or decreased (less)? how much exact reactive power should be maintained? and what should be done for that

2254