We have 2 Nos. Transformer with the capacity of 2000KVA and
1250 KVA and currently using only one 2000KVA T/R during
operational hours while non- operational hous 1250 KVA T/R
also used to reduce T & D losses. Similarly, 2 capacitor
bank of 500KVAR and 300 KVAR also installed to balance
reactive power. Now problem is around 1000 KW load PF is
not maintaning 0.99 as 350 KVAR capacitor is in healty
condtion. Now the PF is maintain 0.95 to 0.96.
Answer Posted / arvind
You please check out the location of the capacitor banks
means whether it is away from the load or not if it is away
from tha load then power losses will be there and affects
the power factor.
secondly, if the load (1000kw) is variable means motor,
then it is difficult to get power factor 0.99.
| Is This Answer Correct ? | 4 Yes | 0 No |
Post New Answer View All Answers
why electron produce magnetic field when it is in motion?
how slip power recovery system work
why can we use cosine wave instead of sine in ac supply as both have same rms vale and ripple factor
HI....HOW CAN BE MESARED THE VALVE OF NEUTRAL GROUND RESISTOR WHIC IS LOCATED AT SWICHGEAR ON GENERATOR SIDE....
circuit diagram of trip circuit supervision relay
How to calulate Locked rotor amper(LRA) for compressor type motors?
EXPLAIN THE TRANSFORMER MAINTENANCE?
Differentiate between ideal and non ideal current sources?
what is mean by kneepoint voltage? when it will happen? ( my doubt is, if CT secondary is open means ct get saturation or blas? what are factors are required for calculations? plz give currect anws:
distribution transformer de-rating formula on over limit iron losses
How to Calculate KA Rating of Main LT Panel
diff. between tension mode & speed mode
What are the main faults of DC generators?
How shall i select the value of capacitor or inductor in a system?
How many types oil using in transformer ? How many letars using in transformer..?