We have 2 Nos. Transformer with the capacity of 2000KVA and
1250 KVA and currently using only one 2000KVA T/R during
operational hours while non- operational hous 1250 KVA T/R
also used to reduce T & D losses. Similarly, 2 capacitor
bank of 500KVAR and 300 KVAR also installed to balance
reactive power. Now problem is around 1000 KW load PF is
not maintaning 0.99 as 350 KVAR capacitor is in healty
condtion. Now the PF is maintain 0.95 to 0.96.
Answer Posted / arvind
You please check out the location of the capacitor banks
means whether it is away from the load or not if it is away
from tha load then power losses will be there and affects
the power factor.
secondly, if the load (1000kw) is variable means motor,
then it is difficult to get power factor 0.99.
Is This Answer Correct ? | 4 Yes | 0 No |
Post New Answer View All Answers
Please brief me about number of pole in alternator.In single phase alternator coils are connected in star or series. How to calculate frequency for the same.
PLZ EXPLAIN THE INTERLOCKING AND CONTROLLING OF CONTACTORS????HOW CAN I DO THAT?
what ispositive, negative, zero sequence impedence?
Explain the different regions in frequency response?
to hook up ten 50 amp rv pedastels at a lenth of 600 feet from the service what size will my service need to be and the size of wire will I have to run to each pedastel in series??????
Explain about how is it working Earth fault'relay and wahts the resistance value of earth bed
draw vector diagram and +ve,zero sequence diagram of symmetrical three phase fault.
how to find ratio of CT & PT in 66/11kv 12 mva supply system ? explain with calculation.
which are the criterias needed to select the kind of neutral earthing(solid earthing,resistance earthing,etc.) at various voltage levels in electrical distribution?
why burdens of VTs is more than CTs?
what & how to check the lightning arrester
What would cause a 240v choke that should give 110v out on a 16w lamp to gradually increase to 160v?
All tape of electrical questions Answers tape of motor transformer e.o.t crane
why the making current is more than then the breaking current and if its true then its about a controling circuit or breaker power contact points
How to find out damper winding failure for synchronous machine?