what happens when d cexcitation given to alternator is
removed while it is running or what happens when dc
excitation is failed in alternator while running?

Answer Posted / abubakr

when excitation is lost due to fault or field breaker
tripping . Reactive power will be supplied by the system and
generator will work as induction generator and its speed
will rise a little . generator which was in over excitation
mode will work in underexcitation .
but there is under excitation limit which should not be
reached so we should detect loss of excitation and trip
generator

Is This Answer Correct ?    11 Yes 4 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

When can we take Neutral as common neutral link?

1209


What are the function of different components of servo motor?

1550


When and where resistance earthing is used ? How to calculate the time constant for earth fault

1327


Can you explain about Restricited earth fault protection scheme

1400


what is the necessity of under ground cables ??

1620






Define what is power quality meter ?

653


how to generator maintenance (A Check, B check,Etc)

1764


working of diesel generator ?

1351


What is the effect on in Zone and out zone fault if Phase side CT is Vk/2<30 mA and Neutral side is CT is Vk/4<30 mA for Transformer REF protection

3078


what is conductor constant of raccun conductor

1771


describe the A.C. Generator Testing procedure

1638


where can the transformer having vector group Yny0 be used??

3582


for 11KV OH system what will be typical per KM "R" "L" "C" parameter. for 33KV OH system what will be typical per KM "R" "L" "C" parameter. for 33KV UG system what will be typical per KM "R" "L" "C" parameter.

1962


Can anyone please give me the parameters , formula needed to calculate the circuit breakers for building services.Thanks

1673


How to setting the volume of RTCC panel AVR (11kv) controller

1172