How to calculate the NGR value for a 2.7MVA Transfomer,
11KV system where the fault current has to be limited to
50A?
Answer Posted / pavan
The value of the NGR to be inserted in the cicuit can be
calculated by the simple formula
R = V / (√3 * I)
Where V is the System Line voltage in Volts
I is the value of the fault current to be limited in your
case it is 50A.
In general practice the fault current is limited to the
full load rating of the largest equipment available in the
system.
| Is This Answer Correct ? | 6 Yes | 4 No |
Post New Answer View All Answers
what is meant by tranformer impedance?
difrent between vcb acb sf6 and mccb breakers
one electromagnet is called
Why reactors use before incoming of ac vvfd drive?
1.Can we use 6.6/11KV 300sq mm xlpe 3core cable for LT use (415 Volt). 2. If we use it for LT then what is the current rating
why we are using Load factor?
what happen if the supply is given to the stator of the 3phase induction motor with out assembling the rotor ?
What is speed mode?
What is EMC filter in VVVF Drive ?
i have been tasked with a design of protection, metering and control(PMC) relay panel extension to accommodate all PMC relays.There is an already existing panel where this one will be built.What are the design aspects for this kind of project? thank you.
What is grid collapse? what is the reason for it?
how to build a network which step down 415v to 1v rms
one conductor length is L.and i am strech uniformly this conductor and made length is 2L.so resistance of this strech conductor is R=4R..but i want to know about area of stech conductor hows it become a/2..
what is the Earth Voltages in Power Plants, Sub-stations, Industries, Residential & Commercial Buildings.
what is mean by Digital Logic Meter (DLM)