How to calculate the NGR value for a 2.7MVA Transfomer,
11KV system where the fault current has to be limited to
50A?
Answer Posted / pavan
The value of the NGR to be inserted in the cicuit can be
calculated by the simple formula
R = V / (√3 * I)
Where V is the System Line voltage in Volts
I is the value of the fault current to be limited in your
case it is 50A.
In general practice the fault current is limited to the
full load rating of the largest equipment available in the
system.
| Is This Answer Correct ? | 6 Yes | 4 No |
Post New Answer View All Answers
what is the AC Plant and how can do the work with parts and picture tell us 150 Tr
How to calculate the multiplying factor for energy meter with ct ratio given
why we use sinosidal voltage / current instead of others in system?
what is excitation/
can anyone provide me a amf panel control wiring using ec-2 relay?
in ACB breaker requireding 3200Amps. buscoupler getting OFF mode and again it reset and getting normal position give me a required answer?
what is servo motor and how to work it.
what is the significance of tan&delta and how it performed in power transformer
WHAT IS MEANT BY OVER EXCITATION IN GENERATOR TRANSFORMERS? DESCRIBE IT.
1.what is the reason for transformer and lightning arrester blast in 33kv system
why are u join ntpc
The 3 phase 400 hp 440 volt slip ring induction motor do not take one phase amps why ? The motor is running good condition
Sir 33kva 2 transformer load 900 amp calc 1800 amp mana jayega
What is ignition module of a CAT Gas Genset G-3508 Engine, Alternator SR4B Series. HOw its checked for correct functioning.Is it repiarable or replacable?
what is difference between 9kv 5ka surge arrester and 9kv 10ka surge arrester.