how much load 15kva dg set can bear.with full explination
and how to calculate?
Answer Posted / amit chaudhary
The full load of 15 Kva DG set will be 12 KW on 0.8 power
factor. if the DG set is 3 phase(415 v) then per phase
current will be I = 15000/(1.732X 415)= 20.86Amp/PHASE
| Is This Answer Correct ? | 28 Yes | 8 No |
Post New Answer View All Answers
What is corkscrew rule?
why we use Test Terminal Block in 11 KV and 33 KV electrical panels.
if we give 60 hz single phase supply to the transformer used in europe , than what will happen
How Calculet The UPS AH In Load
At what speed an electric car can run with 2 HP motor of weighing 400 kg?
how to calculate the surge level of surge suppressors related to the SF6 cicuit breakers?
Why reactive power is needed in a power system? How is it being absorbed or delivered by alternators? For reactive power control we are changing excitation but reactive power absorbing or delivering related to stator. How these two are interlinked? i want a detailed explanation with necessary expressions and figures?
how can i apilly for electrical c licencese.sir,i completed B.Tech in electrical & electronics engineering in 201onot working any company
how wecalculate breaking capcity of acb mcb mccb .explain with example
CAN CU XLPE/PVC CABLE BE USED INPLACE OF LOW NOISE SCREENED CABLE? KINDLY GIVE REASONS
How 3 phase invertor works?
what are your career plans upon completion of the programme and the relevance of recity generation to your professional development?
when we gave dc supply to 220v dc motor its rpm is 1200. then we gave 180v. how many rpm of its motor. gave answer with calculation at my ID.... ravizak@ymail.com
what are the applications of TIG welding
In constant power region of 3-phase IM torque-speed characteristics, if frequency increases flux A does not alter B decreases C increases D none of above