what is the primary current in 415/415 v when secondry of
dry type transformer is shorted.?
Answer Posted / naresh kinger
It will be 139/4.7 x 100 = 3415 AMP on secondry side.
Since ratio is 1/1, primary current will also be 3415 AMP.
Hope it clear now. For any doubt, you can write me at
n.k.kinger@gmail.com
| Is This Answer Correct ? | 2 Yes | 1 No |
Post New Answer View All Answers
i have a 4 Mva transformer 34.5 kv / 480-277 v and i used 2 parallel 3200 amp bus duct for the secondary feeder using 3 ply of bus bar ( 3/8" x 5" ) as a common where the flexible link terminated and 6300 amps breaker for the main, the lower bus duct reaches 70 degrees and the upper bus duct reaches 55 degrees when i used thermal scanner. why the temperature is not balance when the load reaches 3600 amps.