How to calculate KW saving for power factor correction from
0.92 to 0.98 at 350KW load?

Answer Posted / m p narayanan

The question is about the KW saving if pf is improved from
0.92 to 0.98. Answer #1 is silent on the KW saving, but
logically says that 80 KVAR is needed for the pf
improvement (say, by installing a local capacitor bank).
Here , there is a calculation mistake. The value should be
77.99 KVAR instead of 80 KVAR.
Answer #2 also has calculated the same thing and wrongly
declared that it is the KW saving.
The fact is that there is no direct saving in KW by
improving the pf. If 350 KW is needed by the load, it has
to be supplied by the grid. Pf improvement is done for
reducing the KVAR requirement from the grid, not the KW. A
350 KW load at 0.92 pf takes 149.07 KVAR from the grid
whereas the same load of 350 KW at 0.98 pf takes only 71.08
KVAR from the grid, the difference of 77.99 KVAR is
generated locally by the Capacitor bank. The corresponding
KVA at 0.92 pf and 0.98 pf are 380.43 KVA and 357.14 KVA
respectively.
The industries install capacitor banks to improve the pf
with the specific intention of saving electricity bill
because power utilities have a two part tariff – part-1 for
the maximum demand (ie; KVA) and part-2 for the KWH
consumed. This is necessary because the line current is
directly proportional to the KVA and hence the overhead
line conductor size, KVA rating of the transformers
upstream, size of the circuit breakers etc. are dependent
on this. The less the line current, the less will be the
transmission losses. Saving in KW is the result of
reduction in line losses. Hence, as indicated above, there
is no direct saving in KW on account of improvement in pf,
but indirectly the power utility company save KW by
reducing the line losses and also, they save money by
investing less on the size of transformers etc. The quantum
of saving depends on the resistance of the transmission
line, resistance of the transformer windings etc. Hence it
can not be calculated with the available data given in the
question.

Is This Answer Correct ?    5 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

At the starting of dc motor and syn.motor and induction motor high current flowing through the winding. Due to this the windings burnt out. To avoid this different types of starters are used. But incase of transformer what Will be used (At starting no emf is induced in the primary winding)?

1540


If you don’t have coal, salt and copper, then how would you earth your connection temporarily at a camp site.?

1739


Why a tesa lamp is glow between two phase?

1526


why the check zone and main zone are used for Busbar Protn. scheem?

1663


What do you mean by an instrument transformer?

650






Why power factor should not be in leading (capacitive) mode of any load.

5852


HOW TO CALCULATE AMPs OF CURRENT TRANSFORMER IN HT Panel

1802


Which type of questions well asked. ?

1293


How maesure earth neutral value & how much maximum value value required in between earth & neutral.

1585


What is the unit of attenuation?

611


What are the factors which influence the choice of specific magnetic and electric loadings of a synchronous machine?

1593


What is meant by impedance? difference between high & low impedance ?

1561


How can get elongation of 2 k.G aluminium, if elongated aluminium dia is 2.5 mm?

1820


i have 500 amp inductive load of motors ,,,pleas tell me how can i calculate for capacitor bank for improving my power factor to 99 .....calcullations for capacitor bank,,,,

1151


How you calculating the 30 Hp 3 phase AC motor of power what size of cable is used for this motor?

1153