How to calculate KW saving for power factor correction from
0.92 to 0.98 at 350KW load?
Answer Posted / m p narayanan
The question is about the KW saving if pf is improved from
0.92 to 0.98. Answer #1 is silent on the KW saving, but
logically says that 80 KVAR is needed for the pf
improvement (say, by installing a local capacitor bank).
Here , there is a calculation mistake. The value should be
77.99 KVAR instead of 80 KVAR.
Answer #2 also has calculated the same thing and wrongly
declared that it is the KW saving.
The fact is that there is no direct saving in KW by
improving the pf. If 350 KW is needed by the load, it has
to be supplied by the grid. Pf improvement is done for
reducing the KVAR requirement from the grid, not the KW. A
350 KW load at 0.92 pf takes 149.07 KVAR from the grid
whereas the same load of 350 KW at 0.98 pf takes only 71.08
KVAR from the grid, the difference of 77.99 KVAR is
generated locally by the Capacitor bank. The corresponding
KVA at 0.92 pf and 0.98 pf are 380.43 KVA and 357.14 KVA
respectively.
The industries install capacitor banks to improve the pf
with the specific intention of saving electricity bill
because power utilities have a two part tariff – part-1 for
the maximum demand (ie; KVA) and part-2 for the KWH
consumed. This is necessary because the line current is
directly proportional to the KVA and hence the overhead
line conductor size, KVA rating of the transformers
upstream, size of the circuit breakers etc. are dependent
on this. The less the line current, the less will be the
transmission losses. Saving in KW is the result of
reduction in line losses. Hence, as indicated above, there
is no direct saving in KW on account of improvement in pf,
but indirectly the power utility company save KW by
reducing the line losses and also, they save money by
investing less on the size of transformers etc. The quantum
of saving depends on the resistance of the transmission
line, resistance of the transformer windings etc. Hence it
can not be calculated with the available data given in the
question.
| Is This Answer Correct ? | 5 Yes | 0 No |
Post New Answer View All Answers
how to electronic energy metter failed in electomagnectic fild passing in the metter and which thing to defect more on metter.
what is 400kv doble circuit quadpole tower?
what is the transiant condition in alternator? and how it can be prevanted?
What is the formula for calculating impedance of transformers connected parallel at fault level 50KA?
HOW DO YOU CAN CHECK A 15KV DIODE, WHETHER IT IS OK OR NOT?
1600kva capacity Transformers how the bucholz relay,Oil temperature,winding,surge relay relays setting are to be done
What is the principal of motor?
What is stepper motor. What is its uses?
Explain Active power,reactive power,how its related to each other , & inductive ,capacitive.
Why neutral is not used in three phases dol starter
What si the d/f b/w KVA & KWH, kvarh & kvar, kwh & kvar phase voltage & line voltage
i need project topics along with circuit diagram in the electrical and electronics engg and also some websites regarding projets.
Pleae send me last 5 years of Question book about RRB chennai.
in indoor type circuit breakers why only the corner breaker trips specially during cold season. What is the reason.
IF alternator SCR value will be high means what happen in alternator efficency at operating power factor of 0.8