I HAVE A 1 MVA TRANSFORMER, I WANT TO KNOW THE FAULT LEVEL OF
THE SYSTEM ( WHAT IS FAULT LEVEL PLEASE EXPLAIN WITH EXAMPLE)
Answer Posted / shivakumar kinni
1 MVA, 11/0.415kV Transformer
Full load current= 1000000/(1.732x415) = 1391.24A
% Z(Impedance)=5 (As per IS 2026 for transformer ratings of
0.631 MVA to 1.24 MVA)
Fault current= IFL/%Z =1391.24/0.05 =27.824 kA
| Is This Answer Correct ? | 18 Yes | 3 No |
Post New Answer View All Answers
why the projects getting loss?
sir i applied for hpcl(electrical).i want to know from which subjects most of the technical que will b asked.and pattern of the written test.pls help me
why we are not giving the zone 1 trip command to the master trip relay
what is the constructional difference between a power transformer and potentian transformer?
what is RFID? thire application;
The ripple frequency in output of fullwave bridge rectifier is a. Half the input b. Twice the input c. Same as input
What is the difference IN MCCB's between thermal magnetic and electronic tripping system ?
What will be advantage if we put some load in neutral of grounded star transformer & loadshortcircuit current,rated current of cable & MCB with example?
What is dielectric loss?
what happend to DC shunt motor if its field winding insulation becomes slightly weak? will that motor can run on full load or not explain in detail. thanks
i have 3500 amp load and select current transformer and perches.how i calculate .please understand
1)How much current can a 3-1/2 core 100 mm wire carry? 2)What are the special cables required for explosion proof wiring? 3)In case you do not have coal and salt for earthing, how can you achieve good temporary earthing? 4)One horse power single phase motor is more likely to get hot than a one horse power 3 phase motor. Is it true or false, if true why? 5)What are the different types of soft starters for large motors?please explain?
what is the AC Plant and how can do the work with parts and picture tell us 150 Tr
What is the formula for calculating the Instantaneous Short Circuit & overcurrent for any breaker
Hi.. I am a BE GRaduate in E&E. I have 8.5 Experience in Tendering & Estimation field. I have done SAP SD course few years back. But due to some reason i failed to get job in that field and continued my own field. Now I am thinking of changing into SAP seriously. How should i go ahead???