Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

How the neutral earthing is connected in DG alternator

Answer Posted / ram singh

DG Neutral earthing should be connected after neutral
contactor connected towards load side because to avoide
neutral neutral failure to load side which is danger incase
of neutral contactor contact tips carbonise or breakes.
Second reason is to balance load during synchronising.
Third reason is to install REF.

Is This Answer Correct ?    4 Yes 3 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

why using transformer and thyristor switch in 3 phase apfc panel

2883


If mutual flux is 1.2wb & power factor is 0.8 lag , then what is the Useful flux of a transformer?

4491


For RCD (Residual current device) Icu is defined. How i can find Ics for them?

2070


is all the servo motors having brake?please specify which servo motors having brake for stop on position and which are not.

1796


Define active and passive network?

1150


How can we find out LT UG cable fault (size,from-4*25mm sqr to 4*300mm sqr)? How mani types UG cable faults?

3066


What is effect on in zone and out zone fault if CT chosen for phase side is Vk/2<5mA and Neutral side is Vk/2<15mA on REF protection of Transformer

2382


why do we need to use 3c+3e cable, normally i select only 3c+e cable and i think it is enough. pls explain the usefull of 3e cable ( in this project the earthing system is well done)

2477


how to calculate cooling requirement of datacentre from electrical load?

2416


what is the difference between online & offline caliberation of KWH meters. Can Digital meters be caliberated

1981


what is a composite error in current transformers, why occurs & in which it will occur i.e, either metering ct/ protection ct

1861


Mention what are the different colors on wires indicates?

1278


Sir,In our company there are 3 caterpillar make(capacity:(1) 3.3KV,2.5MW(2)3.3KV,2.5MW & (3)3.3KV,1.9MW) & 1 deutz make (capacity:11KV,3.8MW)gas engines utilised,all are running in paralell. There are three transformer utilised,(1) 6.25MVA,3.3KV/22KV,Impedence voltage:6.7% used for two generator,both are 2.5MW(2)5.5MVA,3.3KV/22KV,Impedence voltage:7.2% used for one generator of 2.5MW & (3) 5.5MVA,11KV/22KV,Impedence voltage:7.8% used for one generator of 2.5MW.all generator breakers capacity of 1250Amps. Sir,I want the details of fault level calculation of generator,transformer individually & for whole system. If you require any information from me.feel free for contact me sir.pl.send the answer of my question as the earliest as possible.

2132


what is the difference between interconnection and intraconnections in the circuit diagrams

8400


how much winding resistance of 0.75kw to 12.5kw 3ph sqwiralcage induction motor?

3006