sir,
Two different rating of generator going to connect
parallel, can it set same DROOP or different. Why? Please
explain
Answer Posted / sanu chaudhary
droop means speed regulation. if the machine is running at
1500 rpm at no load and the machine came on full load at
1545 rpm this means the droop of the governor is set 3%.so
if the both machine rating is equal hence droop should be
equaland if rating is diffrent ,droop should diffrent for
smooth operation of system .machine of higher rating should
have set less droop then other for equal load sharing
| Is This Answer Correct ? | 7 Yes | 0 No |
Post New Answer View All Answers
Y phase plates are used in transmission line??? what is there need???
What is the difference b/w fanuc alpha series 16i and 18i controller. what is stand for i
what is difference between window type and wound type transformers?where we will use window type and wound type transformers?
What are the advantages and disadvantages of short-pitched winding?
Explain RLC circuit?
how to select the no. of brushes in a lap winding?
how to know the diffrential relay setting of 06mva step- down (delta-star)transformer?
Explain forward resistance, static resistance and dynamic resistance of a pn junction diode.
USE OF 8 WAY PAN ASSEMBLY
what is meant by loss of field in a DC motor? how a universal motor works?
This is reqd for a 1MW Solar power plant..We have 2DC outputs from the solar panels Connected to 2INVERTOR panels.. Output from invertor is 3ph,280v,500kva,50hz.These are connected to individual ACB.This has to be stepped up to 11KV ,1250KVA SYSTEM.Now can I use (1) one more ACBTO GIVE A COMBINED OUTPUT OF 1000KVA,280V & STEP UP THE OUTPUT BY USING a single two winding 3 ph transformer 11kv/1250kva. or (2)use the two outputs and connect to one three winding transformer of above rating..Pls suggestwith details.
I have a small system with two motors that are running on 380 vac, 60 hz. These motors are expensive and I usally get them from Brazil. I am adding another motor to the system, but I want to purchase a 480 vac, 60 hz motor to use. It will be on a VFD that is rated fro 380 thru 480. Is this posible and will I have to use a larger motor and derate it?
When and where resistance earthing is used ? How to calculate the time constant for earth fault
How to select a contactor? How many types of contactors are available
In how we connect watt meter for open & short circuit test of a single phase transformer.