What should be the DC voltage for Hi-pot test on 11kv switchgear
Answer Posted / gunasekaran
calculation is (2E+1)1.414
(11*2+1)1.414=23*1.414=32.52*.85=28kV already HV test done
at factory so we have applie only 85%of rated voltage
| Is This Answer Correct ? | 12 Yes | 5 No |
Post New Answer View All Answers
How does PLC work for sychronising of Two or more DG sets?
How can we convert 11 kv to 440 volt without using transformer ?
What is “pu” in ee?
Name the component u would expect to find in a switchgear assembly?
What is the direction of current flow in ct secondary...means if the current is flowing from P1 to P2 then what will be the direction of current flow in ct secondaryw
how to differentiate a mpcb,mcb with a contactor? Explain their working operation
HOW TO SELECT THE COPPER CABLE SIZES OF MOTORS,TRANSFORMERS?
how can we say that stator magnetic field rotates with synchronous speed?can we derive?
how do prepare ongc exam.how is it question model.i am electrical. which part covering in electrical.tell me
Define the term Capacitance and Inductance?
why the value of k is more in shell typr transformers?
How to calculate earth wire load by formula
Distribution transformer we provided 2 separate earthing pit for Body and 2 separate earthing pit for neutral,we can not connect separate body earthing pit to other earthing pit but we do metal glanding in secondary side cable termination in both side, transformer and PCC panel (LT Panel), is this safe for transformer and other equipment?