how to do loop checking pls email to
shanavaska2000@yahoo.com
Answer Posted / rahul
For loop checking we are having ILD (instrument loop
drawings)as a documents. for AI we give 4-20ma and chek in
the system if accordingly raw count is coming or not.
for AO we force from the system and check in the plant if
according to raw count current is coming or not.
for ESD loop checking raw count in the system(Triconex) is
819 - 4095 i.e for 4-20ma
if there is problem is loops then we go for backward
checking i.e from system to know where is the problem.
then we do point to point checking.
after completion of loop test we go for functional test.
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
What is force balance principle?
Can Any body tell me how to check Modbus Settings in ER300N L&T trivector meter?
sir ,iam in dem urgent need of HPCL Paper of Instrumentation Branch plz send me at your earliest convenience at ujjwal_sharma1983@yahoo.com
, Instrument Index, P&ID review, I/O schedule, datasheet, DCS / Analyzers specifications, loop diagrams, hook-up drawings.
what is function of switch, and how is it work, explain with difination
what is the calibration procedure for transweigh make weigh feeder?
is there any digitel grevity meter availaible in the market by which we can measure specific gravity of a battery?
Why 4-20 amps is being used in instruments? Why cant we use any other range instead of 4-20 amps? Why only 4 amps is taken as lower limit and why 20 amps is taken as the higher limit?
which type of zones used for boiler? & why ?
We Have Two Field bus Pressure Transmitters of Different Sensor Range (I.E One is of Lower range and Another is of Higher Range).Is same Process Line. My Question is Can i provide Saturation Limit to my field Bus Transmitter as We can provide Saturation current limit to HART Instruments. As During Low Pressure Both Working OK ,But During High Pressure, transmitter with Lower sensor range Goes to Fault mode as Beyond its Sensor Limit it can Measure, So may I provide Saturation point Some where to Suppress This Fault during High Pressure.
this site is owned by an nonsense
What is heating effect?
How to erection of DCS Panel at site step by step
Introduce yourself which is not present in your biodata?
Pl send the model question paper of mahagenco account officer post