Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how to do loop checking pls email to
shanavaska2000@yahoo.com

Answer Posted / rahul

For loop checking we are having ILD (instrument loop
drawings)as a documents. for AI we give 4-20ma and chek in
the system if accordingly raw count is coming or not.
for AO we force from the system and check in the plant if
according to raw count current is coming or not.
for ESD loop checking raw count in the system(Triconex) is
819 - 4095 i.e for 4-20ma
if there is problem is loops then we go for backward
checking i.e from system to know where is the problem.
then we do point to point checking.
after completion of loop test we go for functional test.

Is This Answer Correct ?    2 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

I want to know about DDCMIS in detail ? please explain it. Also give name of reference books in which it is explained in detail in very simple manner.

3798


Explain plc level and its type?

1322


how to change measuring units from mmwc to cubm/h in rosemount air flow transmitter with hart communicator fluke 744

2377


What is three element in drum level?

1380


What is the use of temprature compensation?

1130


what is the procedure of belt scale calibration?

2410


State four different types of flow measurement, for gas flow measurement MMSCFD is the common unit expand the unit and specify significance of word S in the unit.

2000


Speedtronic system .

1948


May I have a brief note above the voltage barriers? Whats is the purpose? Please mail me if you've operational details, mail id: rajkumar.diice@gmail.com

2113


Reason for capillary type dp level transmitter fluctuation

1963


Linear amplifier.

1993


what is vibration a part of proceess variable? if vibration is a part variables then how we minimize the actual vibration on machine on load,? vision of instrumentation contrl plz ans me IPGDL interview question

1895


How d.p. Transmitter can be applied to close tank?

1008


DEAR SIR/MADAM MY NAME IS ARKAPROVA BHATTACHARYYA.I AM A FRESHER INSTRUMENTATION ENGINEER.CAN YOU PLEASE SEND SOME QUESTION PAPERS OF GRADUATE ENGINEER TRAINEE EXAM OF DVC(DAMODAR VALLY CORPORATION).MY EMAIL IDs ARE arka_aec@rediffmail.com.

1885


Please any one can provide latest aptitude test,technical test and interview questions for tata consulting engineering (TCE) i need it asap thanks in advance

1997