in 132 kv substation ligtning arrestor(120 kv) connected to
line. but line voltage comes to 132 kv, it operate or
not???
Answer Posted / vettum perumal
Ligtning Arrestors are connected across one phase and
earth. Hence,the insulation of the arrestor shall be
suitable for only phase voltage. that is, 132kv/root3 =
76KV.Hence, these 120 KV LA will operate very well.
| Is This Answer Correct ? | 26 Yes | 0 No |
Post New Answer View All Answers
how can i reduce sparking without stepdowning the voltage
Can anyone explain me about the capacitor calculation
at work i have a genertor/alternater what is the easyest way to work out if it is dc or ac?
Refernce currents are to be generated using refernce cueernts how can this be done??
what is the Pickup/drop off ratio in BCPU relays
Dear all, I'm manikandan I have done by DIPLOMA EEE from 2011 , I have 5 years of experience from Power plant instrumentation field , which one field is give long life & which one field is best ,I confused a lot and also I'm studying AMIE, can I choose which department from Section B examination? pls tell me
What will be the fault current of any system when its generation is 10% of BASE generation( FUll Load )?Will is 10% or the same as full base calculation?
What is knee point voltage?
Differentiate between digital phase converter and ordinary phase converter.
what is the use of the circle diagram
- two pumps must work with them at the same time but if the first pump start the second pump must delayed for some time to start also , with motor rated power = 90 KW and rated voltage = 380 V and rated power factor = 0.85 lag please draw the power and control circuit for it and determine all circuit components parameters that you use it
how to find out 3 phase complex power in per unit in unbalanced system?
what is the write prosidure of stringing of 8meter pcc pole.
Suppose a 3 phase, 2 pole, 440V induction motor is driving a flywheel of 600mm diameter, 150kg mass. By using v-belt and pulley, the speed is increased to 4500 RPM. What will be the effect on motor current?
What is the best thing to protect the motor from running over full current. CT or O/L or pressure transducer at the given pressure rating