IF i have switchgear with busbar current rating of 1000Amp
35kA then is it necessary to have outgoing breaker kA rating
to be equal to busbar kA rating?

Answer Posted / pravin deshbhratar

yes, whatever fault current rating that we are maintaining
for the Incomer breaker same has to be maintained for
outgoing breaker also unless there is a stepdown
transformer in line. Because the fault level is calculated
on the basis of actual load of the substation that it is
going to carry out, so it is suggested that we have to use
the same KA ratiing for Incomer as well as the Outgoing
breaker.

Is This Answer Correct ?    1 Yes 4 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Draw the vector diagramme for Asynchronous Induction Generator at noload,half load and fullload.

1481


What is the difference between electronic regulator and ordinary electrical rheostat regulator for fans?

657


You are of electrical field and you are going for software? Why

1854


what are the usual topology of transformers at different substations in the power system and why that particular topology is choosen. what are the limitaions of that topology?

1611


If the earth is a good conductor of electricity, why don't people get shocked every time they walking on earth?

1311






What we mean by vintage of an engine+Generator?

1597


best manufacturer for busbar for outdoor switchyard having double bus bar scheme, can any one share technical specification of busbar. 132kv voltage ?

1250


how calculate the electrical load for industry and office

8340


what is the difference between an alternator and a synchronous motor

1570


why high speed tripping relay is used in protection circuit why not normal relay

854


What is the criteria for selecting the voltage classes of an AC Induction Motor.The KW rating above/below which ht/lt selection is made may be provided in details.

1177


rajha power sector details

1541


how calculate gd2 of ht motors

1828


whit is 33kv power 300*300 cable full current with formula

1393


PLEASE ANYBODY HAVE ELECTRICAL CIRCUIT DIAGRAM FOR CHMER PULSE CD 60M SPARKING MACHINE.PLEASE MAIL ME SUPRIYAAYYAPPAN@YAHOO.CO.IN.

2347