i have one transformer 1000kva, 11/.433kv. we are using
200/5 amp. ct unit for measuring purpose, & one 800 amp.
V.C.B Unit for the same t/f operate, i wants to known the primary
current of T/F is only 53 amp. why we used 800 amp.
V.C.B ? & 200/5 amp. CT Unit.
Answer Posted / vinit patil
You are right, you should fight with your electricity board
regarding the HT Metering CT ratio. You should actually
required 100/5 ratio.
But while deasigning VCB it is always prfarable to go on
higher side because it can sustain the heavy short circuit
current. One thing should be noticed that the protection
CTs should be as per the Primary current of the ransformer.
| Is This Answer Correct ? | 5 Yes | 2 No |
Post New Answer View All Answers
I have motor of 3 H.P. How i found the rating of capacitor use in it in single phase motor..???
why capacitance effect is predominant in underground cable transmission and inductance effect is predominant in over head line transmission?
What is the Nyquist criterion regarding control systems?
what is the difference between an alternator and a synchronous motor
How we calculate DC inducation moter Amp? Sir pls give me formula......
typically in power distribution substation. 1- Any idea how would be the graph of capacitor bank consumption verses time through the day . 2- How is the switching ( on and off ) of the capacitor bank, per need?
WANTCONTACT NUMBER & EMAIL/ WEBSITE TO CONTACT THE SECRETARY,MADHYA PRADESH LICENSING BOARD(ELECTRICAL),K- BLOCK,3RD FLOOR,SATPOODA BHAWAN,BHOPAL
How we calculate the Multiplying Factor of Kwh meter for 3 phase alternator.
What will be the diameter of pipe between conservation tank and transformer
How to maintain ac plant?
Ratings of power transformer,Distribution transformer.
What is the abbreviation of NGT panel
what parameters should we check to reduce the power bill
what is charger supervision and control supervision?
i want to run 11kv star connected motor in 6.6kv with delta connected throught inverter, is it possible?