i have one transformer 1000kva, 11/.433kv. we are using
200/5 amp. ct unit for measuring purpose, & one 800 amp.
V.C.B Unit for the same t/f operate, i wants to known the primary
current of T/F is only 53 amp. why we used 800 amp.
V.C.B ? & 200/5 amp. CT Unit.
Answer Posted / vinit patil
You are right, you should fight with your electricity board
regarding the HT Metering CT ratio. You should actually
required 100/5 ratio.
But while deasigning VCB it is always prfarable to go on
higher side because it can sustain the heavy short circuit
current. One thing should be noticed that the protection
CTs should be as per the Primary current of the ransformer.
Is This Answer Correct ? | 5 Yes | 2 No |
Post New Answer View All Answers
how we can come to know that motor winding resistance which showing by DMM is right or wrong???is there any chart or something that we will compare & check???
Hi everyone, I'm Lachuu, recently joined automation company as PLC Engineer. I have certain basic question, I request all big gurus and seniors to answer these question. Because this will be very helpful to me as well starters like me. How to design a control circuit (ex: pick & place - my current project) Yamaha robot PxYx series controller RCX222, using 6 cylinder double acting, plc keyence kv p16r 2 expansion unit for input and output each. How to select panel terminal mcb elcb powersupply. My main concern in some projects how to select dc power supply, mcb rcb(I came across dif bt b c d curves, but stil confusing, pls help me :-(. I would really appreciate all who are going respond to this question.
how is the connection of a 3 phase ct trivector meter done on a pole mounted transformer
how to flameproof electrical motor on the shaft?
What are the various types of BUSBAR Schemes? explain each
What will happen if a dc source is given to a tubelight. Will it work or wont it work....
what is the working process of over & under voltage relay.
can i connect wavetrap in 2 different phase in EHV line?
How may I get the maximum current capacity for a particullar size Alluminum or Copper cable if there is compulsion to use?
How to calculate Air conditioning capacity for a telecom BTS shelter?
how we can find of current direction(supply comming/out going direction) when a transmission line passing through sides.
What is the difference IN MCCB's between thermal magnetic and electronic tripping system ?
Why is ignitor used in sodium vapour lamp
What is ferro-resonance in electrical system? Why it occurs and what are measures to prevent it?
what are the possible reaons & remedies if resistance of NGR getting heat up