if we want ot select cable size with reference to load
current it take than what is the formula and it is same for
aluminium or copper?
Answer Posted / mahesh sali
while selection of cable u should followed the below steps ;
1) cal. the full load current If.L= ( kw / 1.732 x v x
p.f. )
Assume the voltage drop of system as per application says
for motor it should be 10% Vd = 10%
2) Vd = ( 10/100) * v
3) Vd/ph. = ( Vd/1.732 )
4) R = vd/ph./IF.L
5) R-Rho*L/A
Assume , for Copper cable Rho = 1.72 e-8 Ohm-m
L = Length of cable
Base on the above assumation u can easily cal. the size of
cable.
After cal. the cable size , add. 25% extra in ur cal. the
cable size .
Thanking u
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
how does commutator convert a.c to d.c?
Dear all i want to know SEWA Electrical Supervisor Licence test Previous Year Questions ? If any body know please send to me zohairaukllah@yahoo.com
WHY CBCT USE ONLY IN Y PHASE NOT OTHER PHASES
what is the preventive maintence for ht panels and busbars and vcb abd acb's.
If we have to feed a housing complex having load 8MVA, than what would be the better option, either we first step down 33kv supply into 11kv & than 430v or we proposed no of 33/.44 kv transformer, also which option is economical?
raleigh method
working principle of AC Servo Motor with its construction
How to calculate per unit impedance of transformer?
at what base you will tell the direction of rotation of dc motors and generators?
How do i carry out or know the vector group of a Dyn1 and Dyn5 transformer
What was your role in the silicon evaluation/product ramp? What tools did you use?
design of IGBT firing circuit for 11KV
what is the use of expulsition protective gap in 11Kv line.
What is mean by hot and cold loop testing?
EXPLAIN THE ESSENTIAL FACTORS WHICH INFLUENCES THE CHOICE OF SITE FOR A HYDRO ELECTRIC POWER PLANT